<-- Previous Section | | | |
| 95.01 | General Overview |
| 95.02 | Design Criteria |
| 95.03 | Computer Assisted Control Strategies |
| 95.04 | Operating Strategies |
| 95.05 | Troubleshooting |
| 95.06 | Safety |
| 95.07 | Records/Sampling |
The purpose of effluent pumping is to ensure proper discharge of the plant effluent through the outfall. During normal plant operation, the disinfected effluent will exit the Parshall flume into the effluent pipeline and bypass the pump station to the outfall through a flap gate located in the Effluent Junction Box. The pump station will be utilized during periods of high plant flows, high Columbia River water levels, or certain combinations of the two. The pump station will operate whenever the water elevation downstream of the Parshall flume is greater than 24.5 and the differential head between the Parshall flume and Effluent Junction Box is less than 2 ft. The pumps have a common intake header and a common discharge header that discharges to the Effluent Junction Box. When the effluent pumps are operating, the hydraulic pressure of the pump discharge will cause the bypass flap gate to close, ensuring that all effluent passes through the pumps.
The effluent pump station will consist of three variable speed, vertical propeller pumps. Space will be provided for the addition of one future pump. Depending on the flow rate, one or two pumps will operate initially. One redundant pump is provided in case either the lead or lag pump fails or is removed from service. All four of the pumps in the effluent pump station will be identical in design and function. All will be heavy-duty, vertical open-shaft pumps. The pumps will be equipped with adjustable frequency drives for continuous 24-hour duty at any speed within the specified range.
The design criteria for the Effluent Pumps are presented below.95.02 Design Criteria
| Number of Units | |
| Phase II | 3 |
| Ultimate | 4 |
| Type | Vertical propeller |
| Capacity, each | 23 mgd |
| Capacity, Total | |
| Phase II | 46 MGD |
| Ultimate | 64 MGD |
| Total Dynamic Head | 18.5 feet |
| Horsepower, (each) | 100 HP |
| Drive Type, each pump | Variable speed, adjustable frequency |
At the MPWRF, the Effluent Pumps are automatically controlled through the PLC based on the difference in level between the effluent Parshall flume and Effluent Junction Box. The operator selects which mode the PLC uses to run the Effluent Pumps from the SCADA computer located in the Marine Park Administration Building or in the Operator Lab. The operator uses the SCADA computer to monitor alarms and equipment status.
This section tells the operator how to interact with the PLC and the SCADA system, describes each control loop and describes how and where alarm and equipment status is transmitted.
95.03.b.1. Effluent Junction Box
| Loop Function: | Monitor the position of the flap gate and provide a gate open alarm. |
| Instrumentation: | Flap gate switch, ZS-16266 (OPEN)
(Located at the Effluent Junction Box) |
| Control Devices: | None |
| Alarms: | QA-16266 (Flap gate open alarm) |
| PLC/SCS Function: | Monitor OPEN/CLOSE flap gate position switch, ZS-16266 (OPEN) |
Operation:
| Loop Function: | Monitor the difference in level between the effluent Parshall Flume and the Effluent Junction Box and run the effluent pumps based on this difference. |
| Instrumentation: | LET-16221, LET-16222 (Level indicator-Parshall Flume)
(Located downstream of the Effluent Parshall Flume) LET-16225 (Level indicator-Effluent Junction Box) (Located in the Effluent Junction Box) |
| Control Devices: | None |
| Alarms: | None |
| PLC/SCS Functions: | Monitor water level just downstream of the Parshall flume, LET-16221, LET-16222
Monitor water level in Effluent Junction Box, LET-16225 |
Operation:
| Loop Function: | Controls the speed and number of effluent pumps running based on the difference in level between the Parshall Flume and the Effluent Junction Box. Provides pump failure alarms. |
| Instrumentation: | None |
| Control Devices: | HS-16201, HS-16202, HS-16203 (HOR handswitch)
(Located on each AFD panel) HS-16201, HS-16202, HS-16203 (SS push buttons) (Located on each AFD panel) HS-16201, HS-16202, HS-16203 (Auxiliary SS push buttons) (Located at each pump) QL-16201, QL-16202, QL-16203 (PUMP ON light) (Located on each AFD panel) QL-16201, QL-16202, QL-16203 (FAIL light) (Located on each AFD panel) QL-16201, QL-16202, QL-16203 (POWER ON light) (Located on each AFD panel) SI-16201, SI-16202, SI-16203 (Speed Indicator) (Located on each AFD panel) SHK-16201, SHK-16202, SHK-16203 (Pump manual speed control) (Located on each AFD panel) |
| Alarms: | QAR-16201, QAR-16202, QAR-16203 (Pump RUN FAIL in REMOTE)
QAL-16201, QAL-16202, QAL-16203 (Pump RUN FAIL in LOCAL) XQA-16200 (All pumps off/No pumps in REMOTE) |
| PLC/SCS Function: | Monitor pump on status (OOR), QL-16201, QL-16202, QL-16203
Monitor water level downstream of the Parshall flume and provide low water level alarm (OOR), QL-16201, QL-16202, QL-16203 Monitor HOR hand switch REMOTE position (OOR), QL-16201, QL-16202, QL-16203 Monitor local pump fail from AFD and provide alarm (LOCAL FAIL), QL-16201, QL-16202, QL-16203 Determine pump run fail in REMOTE and provide alarm (RUN FAIL), QL-16201, QL-16202, QL-16203 Pump LEAD select hand switch (LEAD 1-3), HS-16200 Provide pump sequencing Provide pump speed signal from level controller, LIK-16200 |
Operation:
In REMOTE mode, each pump can be started and stopped and pump speed can be adjusted by the PLC/SCS system. The LEAD pump may be changed by operations using a SCS CRT hand switch. If the LEAD pump fails, the backup pump is started if it is in REMOTE mode.
There are two modes of REMOTE influent pump sequencing and control, MANUAL and AUTO. The mode selected is used for control of all four effluent pumps. There is a level controller faceplate for AUTO control and sequencing and a manual loading station for each pump at the SCS CRT. When in AUTO mode the level controller will indicate the setpoint and current pump speed. The setpoint cannot be adjusted through the SCS CRT. One of the three setpoints is automatically set based on the number of pumps running. The manual loading stations can be used to adjust individual pump speed in MANUAL mode. The PLC/SCS is programmed for bumpless transfer between modes. Current pump speed is maintained when modes are changed. The number of pumps running may be changed to satisfy AUTO control requirements when selected to AUTO.
When selected to MANUAL mode, the operator may set the speed of pumps and individually start and stop the pumps through the SCS CRT. From the SCS CRT the operator may start a maximum of three pump(s) together.
The pumps are sequenced automatically when selected to AUTO mode. The operator may select the sequencing mode through the SCS CRT. The pumps are started and stopped by the PLC based on the level differential level between the Effluent Junction Box and the level downstream of the Parshall flume as indicated in Table 1 for the respective sequencing modes. The basic strategy is to start pumping when the level downstream of the Parshall flume exceeds 24.5 and the differential between the Effluent Junction Box and the Parshall flume is less than 2 ft. The pumps will be sequenced to maintain the level downstream of the Parshall flume. The pumps will be stopped when the differential level increases above 2 ft and the level downstream of the Parshall flume decreases below 24.5.
|
|
| | Start LEAD pump at minimum speed, no effluent is being pumped
| | Decrease LEAD pump speed to minimum speed. Begin timing sequence; shut off pump after 1 minute if water level downstream of the Parshall Flume remains below 24.5 ft.
| | Increase LEAD pump speed to minimum pumping speed. Increase at Ramp Rate 1 (RR1) until the water level downstream of the effluent Parshall flume is maintained at 24.5 ft.
| | Stop 1st LAG pump. Increase 1st LEAD pump at RR1 to maintain a water level of 24.5 at the Parshall flume effluent.
| | Start 1st LAG pump at minimum speed. Increase at RR1 until the water level downstream of the effluent Parshall flume is maintained at 24.5 ft. Decrease 1st LEAD pump at RR1 and increase 1st LAG pump at RR1 until pump speeds are identical, maintaining a water level of 24.5 at the Parshall flume effluent.
| | Stop 2nd LAG pump. Increase 1st LEAD pump and 1st LAG pump at RR1 to maintain a water level of 24.5 at the Parshall flume effluent.
| | Start 2nd LAG pump at minimum speed. Increase at RR1 until the water level downstream of the effluent Parshall flume is maintained at 24.5 ft. Decrease 1st LEAD pump and 1st LAG pump at RR1 and increase 2nd LAG pump at RR1 until pump speeds are identical, maintaining a water level of 24.5 at the Parshall flume effluent.
| | ||||||||||
The speed of the pumps is varied by the level controllers to match the plant effluent flow. When operating in REMOTE, when a pump fails to run, the STANDBY pump will be called to run in its place. The failed pump will then be dropped from the sequence until the failed condition is cleared. The future pump will be registered by the programming as failed until the pump is installed.
Note: Normal plant operations will use the PLC and SCADA to enter setpoints, select equipment-operating modes and monitor equipment status. If a process can be controlled manually through SCADA, then this will also be included in this section. Local control of equipment will be covered under section 95.04.c. Alternate Operating Conditions. The effluent pumps can be run either in MANUAL or AUTO through the PLC/SCADA system. The SCADA controls are located on the Effluent Pump Control screen. From this screen, the operator can select the desired operating mode and the LEAD, LAG and STANDBY pump. In AUTO, the pumps are started and stopped by the PLC based on the level differential level between the Effluent Junction Box and the level downstream of the Parshall flume. In MANUAL, the operator sets the pump speed and must monitor the level differential. Equipment Status Table 95.04.b.1. summarizes the proper equipment configuration for normal plant operation.95.04.b. Normal Operating Conditions
95.04.b.1. Effluent Pumps (also see section 95.03.b.3.)
|
| Equipment Description | Status
| P-16201 (Effluent Pump # 1) | HOR Handswitch to REMOTE at AFD-16201
| P-16202 (Effluent Pump # 2) | HOR Handswitch to REMOTE at AFD-16202
| P-16203 (Effluent Pump # 3) | HOR Handswitch to REMOTE at AFD-16203
| Effluent Pump Discharge Valve | Open on all pumps
|
| For AUTO operation use the following:
| Pump Control Mode | Select AUTO on SCADA for PLC control of pump speed and sequencing.
| HS-16200 | Select LEAD pump using SCADA.
|
| For MANUAL operation use the following:
| Pump Control Mode | Select MANUAL on SCADA for operator control of pump speed and sequencing.
| SHK-16201, SHK-16202, | Set pump speed for 0 - 100 % on the pump(s) to be run.
SHK-16203 (Pump manual speed control)
| | |||
Note: This section covers plant operations when the PLC has failed and the SCADA system cannot be used as described in section 95.04.b. All equipment control and monitoring is done locally either at the MCC, the AFD panel or the local panel.
Startup
Shutdown
This section not used.
A contingency plan is written to handle an unpredictable occurrence that has a reasonable chance of happening. Most contingency plans deal with situations where having a written procedure can help prevent loss of a unit process, handle a process upset or respond to a hazardous situation. The following is a list of contingency plans developed for the Effluent Pumping process. The plans are kept in the Contingency Plan notebook located in the Operator Laboratory and the Marine Park Supervisor Office.
A Standard Operating Procedure (SOP) is written to handle operator activities performed on a regular but not necessarily daily basis. Most SOP's deal with potentially hazardous activities making it important that a written, step-by-step procedure is available. The following is a list of SOP's developed for the Effluent Pumping process. The procedures are kept in the SOP notebook located in the Operator Laboratory and the Marine Park Supervisor Office.
See Section 75 Maintenance Plan for troubleshooting dealing with the operation of the effluent pumps and the levels sensors.
The operator is responsible for reviewing the SOP on Entering the Effluent Junction Box. A confined space entry form must be filled out and properly signed before entry in the junction box.
Proper lockout procedures are to be followed any time the effluent pumps are serviced.
This section is not used.
95.06. Safety
95.06.a. Confined Spaces
95.06.a.1. Effluent Junction Box
95.06.b. Lockout/Tagout
95.06.b.1. Effluent Pumps
95.07. Records/Sampling
<-- Previous Section