MARINE PARK WATER RECLAMATION FACILITY - Operations and Maintenance Manual

<-- Previous Section
Home
 

Section 95 - Effluent Pumping

95.01General Overview
95.02Design Criteria
95.03Computer Assisted Control Strategies
95.04Operating Strategies
95.05Troubleshooting
95.06Safety
95.07Records/Sampling


95.01 General Overview

The purpose of effluent pumping is to ensure proper discharge of the plant effluent through the outfall. During normal plant operation, the disinfected effluent will exit the Parshall flume into the effluent pipeline and bypass the pump station to the outfall through a flap gate located in the Effluent Junction Box. The pump station will be utilized during periods of high plant flows, high Columbia River water levels, or certain combinations of the two. The pump station will operate whenever the water elevation downstream of the Parshall flume is greater than 24.5 and the differential head between the Parshall flume and Effluent Junction Box is less than 2 ft. The pumps have a common intake header and a common discharge header that discharges to the Effluent Junction Box. When the effluent pumps are operating, the hydraulic pressure of the pump discharge will cause the bypass flap gate to close, ensuring that all effluent passes through the pumps.

The effluent pump station will consist of three variable speed, vertical propeller pumps. Space will be provided for the addition of one future pump. Depending on the flow rate, one or two pumps will operate initially. One redundant pump is provided in case either the lead or lag pump fails or is removed from service. All four of the pumps in the effluent pump station will be identical in design and function. All will be heavy-duty, vertical open-shaft pumps. The pumps will be equipped with adjustable frequency drives for continuous 24-hour duty at any speed within the specified range.

95.02 Design Criteria

The design criteria for the Effluent Pumps are presented below.

Number of Units
     Phase II3
     Ultimate4
TypeVertical propeller
Capacity, each23 mgd
Capacity, Total
     Phase II46 MGD
     Ultimate64 MGD
Total Dynamic Head18.5 feet
Horsepower, (each)100 HP
Drive Type, each pumpVariable speed, adjustable frequency

95.03 Computer Assisted Control Strategies

95.03.a. General Overview

At the MPWRF, the Effluent Pumps are automatically controlled through the PLC based on the difference in level between the effluent Parshall flume and Effluent Junction Box. The operator selects which mode the PLC uses to run the Effluent Pumps from the SCADA computer located in the Marine Park Administration Building or in the Operator Lab. The operator uses the SCADA computer to monitor alarms and equipment status.

95.03.b. Control Strategies

This section tells the operator how to interact with the PLC and the SCADA system, describes each control loop and describes how and where alarm and equipment status is transmitted.

95.03.b.1. Effluent Junction Box

Loop Function:Monitor the position of the flap gate and provide a gate open alarm.
Instrumentation:Flap gate switch, ZS-16266 (OPEN)
(Located at the Effluent Junction Box)
Control Devices:None
Alarms:QA-16266 (Flap gate open alarm)
PLC/SCS Function:Monitor OPEN/CLOSE flap gate position switch, ZS-16266 (OPEN)

Operation:

  1. A timer on the flap gate sensor monitors the time after effluent begins flowing through the effluent pumps. This sensor activates the flap gate open alarm if the gate is still open an adjustable period after the timing sequence is initiated.

95.03.b.2. Effluent Parshall Flume and Effluent Junction Box

Loop Function:Monitor the difference in level between the effluent Parshall Flume and the Effluent Junction Box and run the effluent pumps based on this difference.
Instrumentation:LET-16221, LET-16222 (Level indicator-Parshall Flume)
(Located downstream of the Effluent Parshall Flume)

LET-16225 (Level indicator-Effluent Junction Box)
(Located in the Effluent Junction Box)
Control Devices:None
Alarms:None
PLC/SCS Functions:Monitor water level just downstream of the Parshall flume, LET-16221, LET-16222

Monitor water level in Effluent Junction Box, LET-16225

Operation:

  1. The water levels downstream of the Parshall Flume and within the Effluent Junction Box are monitored to control the operation of the effluent pumps in REMOTE mode. A signal will trigger pump start if the differential head between the two locations is less than 2 ft.

  2. When the LEAD pump starts, it will operate at a minimum speed and will not pump any effluent. When the water level downstream of the Parshall flume exceeds 24.5 ft, the pump speed will be increased and the pump will begin pumping. A warning is initiated if the LEAD pump isn't running and the differential head between the Parshall flume and the Effluent Junction Box is less than 2 ft.

95.03.b.3. Effluent Pumps

Loop Function:Controls the speed and number of effluent pumps running based on the difference in level between the Parshall Flume and the Effluent Junction Box. Provides pump failure alarms.
Instrumentation:None
Control Devices:HS-16201, HS-16202, HS-16203 (HOR handswitch)
(Located on each AFD panel)

HS-16201, HS-16202, HS-16203 (SS push buttons)
(Located on each AFD panel)

HS-16201, HS-16202, HS-16203 (Auxiliary SS push buttons)
(Located at each pump)

QL-16201, QL-16202, QL-16203 (PUMP ON light)
(Located on each AFD panel)

QL-16201, QL-16202, QL-16203 (FAIL light)
(Located on each AFD panel)

QL-16201, QL-16202, QL-16203 (POWER ON light)
(Located on each AFD panel)

SI-16201, SI-16202, SI-16203 (Speed Indicator)
(Located on each AFD panel)

SHK-16201, SHK-16202, SHK-16203 (Pump manual speed control)
(Located on each AFD panel)
Alarms:QAR-16201, QAR-16202, QAR-16203 (Pump RUN FAIL in REMOTE)

QAL-16201, QAL-16202, QAL-16203 (Pump RUN FAIL in LOCAL)

XQA-16200 (All pumps off/No pumps in REMOTE)
PLC/SCS Function:Monitor pump on status (OOR), QL-16201, QL-16202, QL-16203

Monitor water level downstream of the Parshall flume and provide low water level alarm (OOR), QL-16201, QL-16202, QL-16203

Monitor HOR hand switch REMOTE position (OOR), QL-16201, QL-16202, QL-16203

Monitor local pump fail from AFD and provide alarm (LOCAL FAIL), QL-16201, QL-16202, QL-16203

Determine pump run fail in REMOTE and provide alarm (RUN FAIL), QL-16201, QL-16202, QL-16203

Pump LEAD select hand switch (LEAD 1-3), HS-16200

Provide pump sequencing

Provide pump speed signal from level controller, LIK-16200

Operation:

  1. The pumps are sequenced automatically when in the AUTO mode. The PLC starts and stops the pumps based on the level differential between the Effluent Parshall Flume and the Effluent Junction Box (see Table 95.1. in Section 95.04.a. General Operating Strategy).

  2. In the event that a pump fails while the HOR handswitch is in REMOTE, a pump fail signal is sent from the AFD panel to the PLC. The PLC generates a RUN FAIL alarm (QAR-1620X) which is displayed on the SCADA system located in the Operator Laboratory and in the Administration Building. To reset the alarm use the reset button on the Effluent Pump control screen or set the HOR handswitch to OFF. In the event that all pumps shut down and cannot be restarted by the PLC, the PLC sounds alarm QA-16200 (all PUMPS OFF). This alarm is displayed on the SCADA system. To reset this alarm an Effluent Pump must be started. If the operator is running a pump in HAND and the pump fails, the PLC will generate a LOCAL FAIL alarm (QAL-1620X). This alarm is displayed at the AFD panel as well as on the SCADA system. Set the HOR handswitch to OFF to reset the alarm.

95.04 Operating Strategies

95.04.a. General Operating Strategy

In REMOTE mode, each pump can be started and stopped and pump speed can be adjusted by the PLC/SCS system. The LEAD pump may be changed by operations using a SCS CRT hand switch. If the LEAD pump fails, the backup pump is started if it is in REMOTE mode.

There are two modes of REMOTE influent pump sequencing and control, MANUAL and AUTO. The mode selected is used for control of all four effluent pumps. There is a level controller faceplate for AUTO control and sequencing and a manual loading station for each pump at the SCS CRT. When in AUTO mode the level controller will indicate the setpoint and current pump speed. The setpoint cannot be adjusted through the SCS CRT. One of the three setpoints is automatically set based on the number of pumps running. The manual loading stations can be used to adjust individual pump speed in MANUAL mode. The PLC/SCS is programmed for bumpless transfer between modes. Current pump speed is maintained when modes are changed. The number of pumps running may be changed to satisfy AUTO control requirements when selected to AUTO.

When selected to MANUAL mode, the operator may set the speed of pumps and individually start and stop the pumps through the SCS CRT. From the SCS CRT the operator may start a maximum of three pump(s) together.

The pumps are sequenced automatically when selected to AUTO mode. The operator may select the sequencing mode through the SCS CRT. The pumps are started and stopped by the PLC based on the level differential level between the Effluent Junction Box and the level downstream of the Parshall flume as indicated in Table 1 for the respective sequencing modes. The basic strategy is to start pumping when the level downstream of the Parshall flume exceeds 24.5 and the differential between the Effluent Junction Box and the Parshall flume is less than 2 ft. The pumps will be sequenced to maintain the level downstream of the Parshall flume. The pumps will be stopped when the differential level increases above 2 ft and the level downstream of the Parshall flume decreases below 24.5.

TABLE 95.1. - PUMP SEQUENCING MODE
Differential of Water Elevation Between Parshall Flume and the Effluent Junction Box (Feet)
Action
Decreasing Differential
Increasing Differential
2
 Start LEAD pump at minimum speed, no effluent is being pumped
 
2
Decrease LEAD pump speed to minimum speed. Begin timing sequence; shut off pump after 1 minute if water level downstream of the Parshall Flume remains below 24.5 ft.
< 2
 Increase LEAD pump speed to minimum pumping speed. Increase at Ramp Rate 1 (RR1) until the water level downstream of the effluent Parshall flume is maintained at 24.5 ft.
 
< 2
Stop 1st LAG pump. Increase 1st LEAD pump at RR1 to maintain a water level of 24.5 at the Parshall flume effluent.
< 2
 Start 1st LAG pump at minimum speed. Increase at RR1 until the water level downstream of the effluent Parshall flume is maintained at 24.5 ft. Decrease 1st LEAD pump at RR1 and increase 1st LAG pump at RR1 until pump speeds are identical, maintaining a water level of 24.5 at the Parshall flume effluent.
 
< 2
Stop 2nd LAG pump. Increase 1st LEAD pump and 1st LAG pump at RR1 to maintain a water level of 24.5 at the Parshall flume effluent.
< 2
 Start 2nd LAG pump at minimum speed. Increase at RR1 until the water level downstream of the effluent Parshall flume is maintained at 24.5 ft. Decrease 1st LEAD pump and 1st LAG pump at RR1 and increase 2nd LAG pump at RR1 until pump speeds are identical, maintaining a water level of 24.5 at the Parshall flume effluent.

The speed of the pumps is varied by the level controllers to match the plant effluent flow. When operating in REMOTE, when a pump fails to run, the STANDBY pump will be called to run in its place. The failed pump will then be dropped from the sequence until the failed condition is cleared. The future pump will be registered by the programming as failed until the pump is installed.

95.04.b. Normal Operating Conditions

Note: Normal plant operations will use the PLC and SCADA to enter setpoints, select equipment-operating modes and monitor equipment status. If a process can be controlled manually through SCADA, then this will also be included in this section. Local control of equipment will be covered under section 95.04.c. Alternate Operating Conditions.

95.04.b.1. Effluent Pumps (also see section 95.03.b.3.)

The effluent pumps can be run either in MANUAL or AUTO through the PLC/SCADA system. The SCADA controls are located on the Effluent Pump Control screen. From this screen, the operator can select the desired operating mode and the LEAD, LAG and STANDBY pump. In AUTO, the pumps are started and stopped by the PLC based on the level differential level between the Effluent Junction Box and the level downstream of the Parshall flume. In MANUAL, the operator sets the pump speed and must monitor the level differential. Equipment Status Table 95.04.b.1. summarizes the proper equipment configuration for normal plant operation.

EQUIPMENT STATUS TABLE 95.04.b.1.
Equipment DescriptionStatus
P-16201 (Effluent Pump # 1)HOR Handswitch to REMOTE at AFD-16201
P-16202 (Effluent Pump # 2)HOR Handswitch to REMOTE at AFD-16202
P-16203 (Effluent Pump # 3)HOR Handswitch to REMOTE at AFD-16203
Effluent Pump Discharge ValveOpen on all pumps
For AUTO operation use the following:
Pump Control ModeSelect AUTO on SCADA for PLC control of pump speed and sequencing.
HS-16200Select LEAD pump using SCADA.
For MANUAL operation use the following:
Pump Control ModeSelect MANUAL on SCADA for operator control of pump speed and sequencing.
SHK-16201, SHK-16202,Set pump speed for 0 - 100 % on the pump(s) to be run. SHK-16203 (Pump manual speed control)


95.04.c. Alternate Operating Conditions

Note: This section covers plant operations when the PLC has failed and the SCADA system cannot be used as described in section 95.04.b. All equipment control and monitoring is done locally either at the MCC, the AFD panel or the local panel.

95.04.d. Startup/Shutdown Conditions

Effluent Pumps

Startup

  1. Verify that the discharge valving on the effluent pumps is in the open position.
  2. Verify that all level detectors are operational and giving accurate readings.
  3. Place the HOR handswitch position to REMOTE on all available pumps.

Shutdown

  1. Place the HOR handswitch position to OFF and power down the AFD.
  2. Close the discharge valve to finish isolating the pump.

95.04.e. Key Control Data and 4 Level Alarm Table

This section not used.

95.04.f. Contingency Plans

A contingency plan is written to handle an unpredictable occurrence that has a reasonable chance of happening. Most contingency plans deal with situations where having a written procedure can help prevent loss of a unit process, handle a process upset or respond to a hazardous situation. The following is a list of contingency plans developed for the Effluent Pumping process. The plans are kept in the Contingency Plan notebook located in the Operator Laboratory and the Marine Park Supervisor Office.

95.04.g. Standard Operating Procedure

A Standard Operating Procedure (SOP) is written to handle operator activities performed on a regular but not necessarily daily basis. Most SOP's deal with potentially hazardous activities making it important that a written, step-by-step procedure is available. The following is a list of SOP's developed for the Effluent Pumping process. The procedures are kept in the SOP notebook located in the Operator Laboratory and the Marine Park Supervisor Office.

95.05. Troubleshooting

See Section 75 Maintenance Plan for troubleshooting dealing with the operation of the effluent pumps and the levels sensors.

95.06. Safety

95.06.a. Confined Spaces

95.06.a.1. Effluent Junction Box

The operator is responsible for reviewing the SOP on Entering the Effluent Junction Box. A confined space entry form must be filled out and properly signed before entry in the junction box.

95.06.b. Lockout/Tagout

95.06.b.1. Effluent Pumps

Proper lockout procedures are to be followed any time the effluent pumps are serviced.

95.07. Records/Sampling

This section is not used.


<-- Previous Section
Home