<-- Previous Section | Next Section --> | |
| 45.01 | General Overview |
| 45.02 | Design Criteria |
| 45.03 | Computer Assisted Control Strategies |
| 45.04 | Operating Strategies |
| 45.05 | Troubleshooting |
| 45.06 | Safety |
| 45.07 | Records/Sampling |
The chemical delivery system is intended to accurately deliver necessary quantities of two chemicals, sodium hypochlorite and sodium hydroxide (NaOCl and NaOH), to various points throughout the treatment plant. The system has four independent subsystems, each serving one or more application points.
The design criteria for the Screenings/Headworks Buildings Air Treatment System is presented below.
STORAGE TANKS
|
| Number of Units
| Initial | 4 (3 NaOCl, 1 NaOH)
| Size
| NaOCL Diameter | 10 feet
| Height | 12 feet
| Volume | 7050 gallons
| NaOH Diameter | 8 feet
| Height | 10.75 feet
| Volume | 4000 gallons
| | |
METERING PUMPS
| APPLICATION POINT (chemical) | No. Pumps | Pump Tags | Pump Capacity (GPH), Each
| Secondary Clarifier Launder (NaOCl) | 1.00 | P-17021 | 5-50
| Primary Clarifier Launder (NaOCl) | 1.00 | P-17021 | 5-50
| Grit Chamber Effluent (NaOCl) | 1.00 | P-17021 | 5-50
| Wet Well (NaOCl) | 1.00 | P-17021 | 5-50
| RAS Line (NaOCl) | 1.00 | P-17021 | 5-50
| Primary Sludge Pumps (NaOCl) | 1.00 | P-17024 | 2-20
| WAS Pumps (NaOCl) | 1.00 | P-17027 | 2-20
| Odor Control Scrubber (NaOCl) | 2.00 | P-17025 | P-17026 3-30
| W3 Wet Well (NaOCl) | 2.00 | P-17022 | P-17023 2-20
| Odor Control Scrubber (NaOH) | 2.00 | P-17201 | P-17202 0.4-4
| |
At the MPWRF, the operator has the ability to apply Sodium Hypochlorite (NaOCl) to various points throughout the treatment plant. The operator has the ability to start and stop the chemical feed pumps and adjust the stroke through the SCS CRT. The PLC monitors pump operation and will sound an alarm in case of pump failure. Chemical storage tank levels are also monitored by the PLC and an alarm will sound at high and low tank levels.
This section tells the operator how to interact with the PLC and the SCS, describes each control loop and describes how and where alarm and equipment status is transmitted.
45.03.b.1. Shock Application System
| Loop Function: | Controls the addition of Sodium Hypochlorite to the Secondary Clarifier launder, Primary Clarifier launder, Grit Chamber effluent, Influent Pump Station wet well and the RAS line. |
| Control Devices: | HS-17021 (HOR Handswitch)
(Located at LP-17020) HS-17021 (SS Push-buttons) (Located at LP-17020) QL-17021 (Pump ON light) (Located at LP-17020) ZHK-17021 (Pump manual STROKE control) (Located at LP-17020) ZI-17021 (Pump STROKE indicator) (Located at LP-17020) |
| Alarms: | QA-17021 (Pump P-17021 FAIL) |
| PLC/SCS Function: | Monitor pump on status (OOR), QL-17021
Monitor HOR handswitch REMOTE position (OOR), QL-17021 Determine REMOTE pump fail and provide alarm, QA-17021 |
Operation:
| Loop Function: | Controls the addition of Sodium Hypochlorite to the Primary Sludge and WAS pumps. |
| Control Devices: | HS-17024, HS-17027 (HOR Handswitch)
(Located at LP-17020) HS-17024, HS-17027 (SS Push-buttons) (Located at LP-17020) QL-17024, HS-17027 (Pump ON light) (Located at LP-17020) ZHK-17024, ZHK-17027 (Pump manual STROKE control) (Located at LP-17020) ZI-17024, HS-17027 (Pump STROKE indicator) (Located at LP-17020) |
| Alarms: | QA-17024 (Pump P-17024 FAIL)
QA-17027 (Pump P-17027 FAIL) |
| PLC/SCS Functions: | Monitor pump on status (OOR), QL-17024, QL-17027
Monitor HOR handswitch REMOTE position (OOR), QL-17024, QL-17027 Determine REMOTE pump fail and provide alarm, QA-17024, QA-17027 |
Operation:
| Loop Function: | Controls the addition of Sodium Hypochlorite to the W3 Pump Station wet well. |
| Control Devices: | HS-17022, HS-17023 (HOR Handswitch)
(Located at LP-17020) HS-17022, HS-17023 (SS Push-buttons) (Located at LP-17020) QL-17022, HS-17023 (Pump ON light) (Located at LP-17020) ZHK-17022, ZHK-17023 (Pump manual STROKE control) (Located at LP-17020) ZI-17022, HS-17023 (Pump STROKE indicator) (Located at LP-17020) |
| Alarms: | QA-17022 (Pump P-17022 FAIL)
QA-17023 (Pump P-17023 FAIL) |
| PLC/SCS Function: | Monitor pump on status (OOR), QL-17022, QL-17023
Monitor HOR handswitch REMOTE position (OOR), QL-17022, QL-17023 Determine REMOTE pump fail and provide alarm, QA-17022, QA-17023 Provide LEAD pump selector handswitch (LEAD 1-2), HS-17022 |
Operation:
Note: The operation of the Air Treatment System NaOCl and NaOH pumps is described in section 40.03.b.5.
In the REMOTE mode, the Shock Application Feed Pump can be started and stopped and its stroke adjusted manually through the SCS CRT. A manual loading station faceplate at the SCS CRT allows operating personnel to make pump stroke adjustments.
When selected to REMOTE there are two modes for operating the Sludge Application Feed Pump control; MANUAL and AUTO. In MANUAL mode, each pump can be started and stopped and its stroke adjusted through the SCS CRT. Manual loading station faceplates allow personnel to make pump stroke adjustments. In AUTO mode P-17024 is started whenever a Primary Sludge Pump or Primary Scum Transfer Pump is on. In AUTO mode P-17027 is started whenever the WAS or Secondary Scum Transfer pump is on. In AUTO the pump stroke is adjusted to the value set by operating personnel at the SCS CRT manual loading station.
The LEAD pump for the Plant Water Supply Feed Pump is selected using a switch at the SCS CRT. When selected to REMOTE there are two modes for pump control; MANUAL and RATIO. The pumps function in MANUAL in a manner similar to the sludge transport NaOCL pumps.
When selected to RATIO mode, the NaOCL pump stroke is adjusted to maintain a desired ratio of NaOCL flow to W3 flow. W3 flow is measured by flow meter FIT-16311. Personnel can enter the desired ratio setpoint using a faceplate at the SCS CRT. When the plant water supply NaOCL pump function is in RATIO mode the NaOCL dose is automatically adjusted as the W3 pumps transition between small and large pumps.
The operation of the odor control NaOCL and NaOH pumps is described in the Air Treatment System narrative.
Note: Normal plant operation will use the PLC and the SCS CRT to enter setpoints, select equipment operating modes and monitor equipment status. If a process can be controlled manually through the SCS CRT then this will also be included in this section.
Local control of equipment will be covered under section 45.04.c. Alternate Operating Conditions.
The Shock Application Chemical Feed Pump is run in MANUAL through the PLC/SCS system. The SCS CRT controls are located on the Shock Application System screen. The operator can start and stop the pump and adjust pump speed and stroke using the SCS CRT manual loading station. Dilution water is added to the Sodium Hypochlorite using rotameter FI-17071 located in the Chemical Building. Dosing and application points are controlled using rotameters FI-17081 through FI-17085 also located in the Chemical Building. The operator will also be responsible for opening the appropriate valves in the field so the Sodium Hypochlorite is fed to the proper application point. Equipment Status Table 45.04.b.1 summarizes the proper equipment configuration for normal plant operation.
|
| Equipment Description | Status
| P-17021 (Sodium Hypochlorite Chemical Feed Pump) | HOR handswitch to REMOTE at LP-17020
| Chemical Feed Pump Suction Valve | Open
| Chemical Pump Discharge Valve | Open
| FI-17071 (W3 Dilution Water Rotameter) | On-line
| FI-17081 (CS1 Rotameter) | On-line if feeding to Plant Influent
| FI-17082 (CS2 Rotameter) | On-line if feeding to Grit Chamber Effluent
| FI-17083 (CS5 Rotameter) | On-line if feeding to RAS Line
| FI-17084 (CS4 Rotameter) | On-line if feeding to Secondary Clarifier Launders
| FI-17085 (CS3 Rotameter) | On-line if feeding to Primary Clarifier Launders
| | |
The Sludge Transport Chemical Feed Pumps can be run in either AUTO or MANUAL through the PLC/SCS system. The SCS CRT controls are located on the Sludge Transport System screen. In AUTO mode, the PLC will start and stop the chemical pumps whenever a Primary Sludge Pump, Primary Scum Transfer Pump, WAS Pump or Secondary Scum Transfer Pump is on. The operator is responsible for setting pump speed and stroke setpoints on the SCS CRT manual loading station. In MANUAL the operator can start and stop the pumps and adjust pump speed and stroke through the SCS CRT. The operator will also be responsible for opening the appropriate valves in the field so the Sodium Hypochlorite is fed to the proper application point. Equipment Status Table 45.04.b.2 summarizes the proper equipment configuration for normal plant operation.
|
| Equipment Description | Status
| P-17024 (Sodium Hypochlorite Chemical Feed Pump to the Primary Sludge Line) | HOR handswitch to REMOTE at LP-17020
| P-17027 (Sodium Hypochlorite Chemical Feed Pump to the WAS Line) | HOR handswitch to REMOTE at LP-17020
| Chemical Feed Pump Suction Valve | Open to both pumps
| Chemical Pump Discharge Valve | Open to both pumps
| | |
The Plant Water Supply Chemical Feed Pumps can be run in either RATIO or MANUAL through the PLC/SCS system. The SCS CRT controls are located on the Plant Water Supply System screen. In RATIO mode, the PLC will start and stop the chemical pumps to maintain a desired ratio of Sodium Hypochlorite feed to the W3 flow. The operator is responsible for setting pump speed and stroke setpoints on the SCS CRT manual loading station. In MANUAL the operator can start and stop the pumps and adjust pump speed and stroke through the SCS CRT. Dilution water is added to the Sodium Hypochlorite using rotameter FI-17072 located in the Chemical Building. The operator will also be responsible for opening the appropriate valves in the field so the Sodium Hypochlorite is fed to the proper application point. Equipment Status Table 45.04.b.3 summarizes the proper equipment configuration for normal plant operation.
|
| Equipment Description | Status
| P-17022 (Sodium Hypochlorite Chemical Feed Pump to the W3 Wet Well) | HOR handswitch to REMOTE at LP-17020
| P-17023 (Sodium Hypochlorite Chemical Feed Pump to the W3 Wet Well) | HOR handswitch to REMOTE at LP-17020
| FI-17072 (W3 Dilution Water Rotameter) | On-line
| Chemical Feed Pump Suction Valve | Open to both pumps
| Chemical Pump Discharge Valve | Open to both pumps
| | |
Blank.
Not used.
A contingency Plan is written to handle an unpredictable occurrence that has a reasonable chance of happening. Most Contingency Plans deal with situations where having a written procedure can help prevent loss of a unit process, handle a process upset or respond to a hazardous situation. The following is a list of Contingency Plans developed for the Chemical Delivery System process. The plans are kept in the Contingency Plan Notebook located in the Operator Laboratory and the Shift Supervisor Office.
A Standard Operating Procedure (SOP) is written to handle operator activities performed on a regular but not necessarily daily basis. Most SOPs deal with potentially hazardous activities making it important that a written, step-by-step procedure be available. The following is a list of SOPs developed for the Chemical Delivery System process. The procedures are kept in the SOP Notebook located in the Operator Laboratory and the Shift Supervisor Office.
See Section 75 Maintenance Plan for trouble shooting dealing with the operation of the chemical feed pumps.
The operator is responsible for reviewing the SOP on Entering the Chemical Storage Tanks. A confined space entry form must be filled out and properly signed before entry into the tanks.
Not used.
<-- Previous Section | Next Section --> | |