<-- Previous Section | Next Section --> | |
| 35.01 | General Overview |
| 35.02 | Design Criteria |
| 35.03 | Computer Assisted Control Strategies |
| 35.04 | Operating Strategies |
| 35.05 | Troubleshooting |
| 35.06 | Safety |
| 35.07 | Records/Sampling |
The purpose of disinfection is to destroy disease-causing organisms in the final effluent prior to ultimate discharge into the receiving water. The means of disinfection is ultraviolet (UV) radiation. Secondary effluent flows from the secondary clarifiers into a flow splitting box at the influent to the UV channels. Flow split is accomplished based on headloss over a rectangular weir. The flow in each channel passes through a manually-cleaned bar screen which intercepts materials that could foul or damage the UV lamps. A counter-weighted flap gate at the discharge end of each channel maintains a constant water surface elevation in each channel. A motorized slide gate at the entrance to each channel provides isolation when a channel is shutdown for flow pacing or maintenance.
After leaving the UV channels, effluent flows through a small withdrawal well where non-potable plant water and reuse water (wetlands enhancement and/or irrigation) can be removed from the flow stream. The remaining effluent flows through the parshall flume before discharge to the outfall structure in the Columbia River.
The UV dose is adjusted based on effluent flow measurement. Banks of UV modules are energized/de-energized and UV channels put into and out of service as plant flows vary. One bank of modules in each channel will remain energized whenever the channel is in service to base load the channel. Service hours are equalized by rotating the lead bank to the bank with the least run time every time the lead channel rotates. The flow setpoints are as follows:
Channel No.3 has the capability to operate isolated from the secondary effluent flow. Slide gates control the isolation of this channel. When wetlands treatment is not required, this channel is available to operate in parallel with the remaining channels. In addition to isolation slide gates in the influent and effluent channels, a motorized slide gate controls the channel influent flow in the same manner as the other two channels and a sluice gate is used to isolate the discharge pipe to the wetlands.
Upon expansion of the effluent treatment complex, the northern most UV channel will remain the "wetlands treatment channel" and piping to the existing "wetlands" channel No.3 will be re-routed.
The UV control system for the wetlands treatment channel is operated manually while disinfecting the wetlands flow stream and in flow pacing mode while disinfecting the plant effluent flow stream. The wetlands treatment system is not required for the plant effluent flow treatment capacity and can serve as a backup plant effluent disinfection system.
Regular cleaning and inspection of the UV lamps is required to maintain effluent disinfection quality. Cleaning involves removing the modules from the channels. To accommodate this maintenance activity a UV cleaning system is provided. A bridge crane is used to remove UV modules or an entire UV bank from the channels and transport them to the cleaning area. A curbed hose down area is provided to remove loose material from the modules. The modules or banks are then lowered into a basin where an acidic cleaning solution removes scale build-up. A diffused air system agitates the cleaning basin to further enhance material removal. A dilute concentration of citric or phosphoric acid is most commonly used as a cleaning solution.
Three UV channels will be built as part of the Phase I work. Each channel is wide enough for 23 UV modules in each bank. To meet specified treatment criteria, only 19 modules per bank are supplied. Space equal to the size of 2 modules are installed on each side of each bank for the addition of future modules. Each bank is constructed to accommodate the future number of modules. Using future modules will not increase the flow capacity of each channel, but will increase the level of disinfection achieved.
Six additional channels will be constructed at ultimate buildout. Provisions will be made so that the buildout facility will utilize the Phase I cleaning equipment, including the bridge crane, and the effluent discharge channel. Ultimate effluent flow measurement will be accomplished by removing the Phase I, or interim phase, parshall flume insert from the six-foot parshall flume provided in Phase I.
35.02 Design Criteria
DISINFECTION BASINS
|
| Number of Basins
| Phase 1 | 3
| Phase 2 | 6 (3 existing, 3 new)
| Ultimate | 8 (add equipment to 2 channels)
| Basin Dimensions
| Length | 50'-0"
| Width | 4'-0.5"
| Depth | 5'-0"
| Sidewater Depth | 2'-0" nominal water depth
| Influent TSS | 30 mg/l
| Peak Design Flow
| Phase 1 | 20.8 mgd
| Phase 2 | 41.6 mgd
| Ultimate | 63 mgd
| Minimum Design Flow
| Phase 1 | 2.2 mgd
| Phase 2 | 4.4 mgd
| Ultimate | 6.7 mgd
| UV Transmissivity | 65 percent
| Effluent Disinfection Standard (Fecal Coliform)
| Design | 200 MPN/100 ml
| Future Provisions | 30 MPN/100 ml
|
| ULTRAVIOLET DISINFECTION SYSTEM
|
| Number of Modules
| Phase 1 | 207
| Phase 2 | 414
| Ultimate | 552
| Module description
| Modules/bank | 23
| Lamps/module | 8
| Power Consumption | 0.26 Kw/module
| Ballast Type | Electronic
| Lamp Configuration | Horizontal
|
| ULTRAVIOLET CLEANING SYSTEM
|
| Cleaning Basin
| Dimensions (LxWxD) | 5'x7'x6'
| Lining | Polyethylene
| Agitation System
| Blower | Rotary Lobe
| Diffusers | PVC
| Overhead Bridge Crane
| Capacity | 1 ton
| Type | Top running
| Crane Speed | 70 fpm
| Trolley Speed | 65 fpm
| Hoist Speed | 45 fpm (variable)
|
| EFFLUENT FLOW MEASUREMENT
|
| Type | Parshall Flume
| Number of Units | 1
| Size
| Phase I | 2 foot
| Ultimate | 6 foot
| Minimum Capacity
| Phase I | 1.1 mgd
| Ultimate | 6.7 mgd
| Maximum Capacity
| Phase I | 20.8 mgd
| Ultimate | 63.0 mgd
| | ||||
At the MPWRF, the UV disinfection system is controlled through the System Control Center (SCC) located in the Effluent Disinfection Building. The operator uses a panelview system at the SCC to monitor alarms and change system variables. The operator can also use the SCS to monitor alarms and equipment status of the UV system.
This section tells the operator how to interact with the SCC and the SCS systems, describes each control loop and describes how and where alarm and equipment status is transmitted.
35.03.b.1. UV Influent Channel Gates
| Loop Function: | Opens and closes disinfection channels to meet the needs of the disinfection system based on influent flow rate. Monitors the gate position (open/closed) and sounds an alarm if the gate fails to open or close properly. |
| Instrumentation: | ZS-16011, ZS-16012, ZS-16013, ZS-16214, ZS-16215, ZS-16216 (Monitor OPEN/CLOSED [OC] gate position switch)
(Located at each influent gate) |
| Control Devices: | HS-16011, HS-16012, HS-16013, HS-16214, HS-16215, HS-16216 (OPEN/STOP/CLOSE [OSC] handswitch)
(Located at each influent gate) HS-16011, HS-16012, HS-16013, HS-16214, HS-16215, HS-16216 (LOCAL/OFF/REMOTE [LOR] handswitch) (Located at each influent gate) |
| Alarms: | QA-16001 (UV Channel No. 1 MAJOR ALARM)
QA-16001 (UV Channel No. 1 MAJOR ALARM) QA-16002 (UV Channel No. 2 MAJOR ALARM) QA-16003 (UV Channel No. 3 MAJOR ALARM) QA-16204 (UV Channel No. 4 MAJOR ALARM) QA-16205 (UV Channel No. 5 MAJOR ALARM) QA-16206 (UV Channel No. 6 MAJOR ALARM) |
| PLC/SCS Function: | Monitor OPEN/CLOSE gate position switches (OC), ZS-16011, ZS-16012, ZS-16013, ZS-16214, ZS-16215, ZS-16216
Monitor LOR handswitch REMOTE position (REMOTE), QL-16011, QL-16012, QL-16013, QL-16214, QL-16215, QL-16216 |
Operation:
| Loop Function: | Turns on and shuts off UV lamps to meet the needs of the disinfection system based on the influent flow. Monitors lamp intensity, single and multiple lamp failures, and checks lamp module performance. The system also monitors run times for each individual module so the operator can track lamp usage. If the SCC detects any failure in the UV lamp array, it will generate an alarm. |
| Instrumentation: | Allen-Bradley 2711-TCI PanelView Touch Screen
(Located on LP-16000) |
| Alarms: | The SCC will display the following alarm messages:
|
Operation:
| Loop Function: | Opens and closes the channel drain valves as required to meet the needs of the disinfection system based on the influent flow. |
| Control Devices: | None provided |
| Alarms: | QA-16161 (Channel drain valve FV-16161 failed)
QA-16162 (Channel drain valve FV-16162 failed) QA-16163 (Channel drain valve FV-16163 failed) QA-16264 (Channel drain valve FV-16264 failed) QA-16265 (Channel drain valve FV-16265 failed) QA-16266 (Channel drain valve FV-16266 failed) |
| PLC/SCS Function: | Monitor OPEN/CLOSE channel drain valve position switches (OC), ZS-16161, ZS-16162, ZS-16163, ZS-16264, ZS-16265, ZS-16266
Determine drain valve fail to open or close alarm (FAIL), QA-16161, QA-16162, QA-16163, QA-16264, QA-16265, QA-16266 Provide sequencing of channel drain valves |
Operation:
| Loop Function: | Monitors the on status of the low pressure blower for the UV Cleaning Basin. |
| Control Devices: | HS-16061 (HAND/OFF/REMOTE [HOR] handswitch)
(Located at MCC-10) HS-16061 (START/STOP (SS) push-buttons) (Located at MCC-10) QL-16061 (Blower on light [ON]) (Located at MCC-10) HS-16061 (Auxiliary START/STOP [SS] push-buttons) (Located at the blower) |
| Alarms: | None associated with this loop. |
| PLC/SCS Function: | Monitor blower on status (OOR), QL-16061 |
Operation:
The influent channel gates are opened and closed manually by placing the LOR in LOCAL and using the OSC handswitch. The gates are controlled by the System Control Center (SCC) when the handswitch is placed in REMOTE.
The UV banks and influent channel gates in each disinfection channel are controlled by the System Control Center (SCC, LP-16000). The operator can monitor alarms and change system variables through a programmable user interface consisting of a CRT and keyboard mounted on the SCC. The SCC receives a 4 - 20 mAdc plant flow signal from the plant PLC located in LCP-16. The SCC uses the flow signal to turn the lamp banks on and off and to open and close the channel gates. For a detailed description of operations and user adjustable parameters see the UV manufacturer's control description.
The flow pacing signal is a 4 to 20 mA analog signal produced by the plant PLC in LCP-16. When the SCC is in flow pacing mode, it receives the 4 to 20 mA signal from the plant PLC and automatically adjusts the number UV lamps that are energized and number of channels in service in proportion to the signal.
Whenever a UV channel is taken out of service (its influent gate closed), the channel drain valve at the end of the channel is opened to drain the channel. The drain valve remains open until the channel is placed back into service to prevent water from collecting in the channel.
Note: Normal plant operation will use the PLC and the SCS CRT to enter setpoints, select equipment operating modes and monitor equipment status. If a process can be controlled manually through the SCS CRT then this will also be included in this section. Local control of equipment will be covered under Section 35.04.c., Alternate Operating Conditions.
The UV System Control Center (SCC) opens and closes the gates based on the flow signal from flow meter FE/FIT-16041 located at the effluent Parshall flume. The flow setpoints are entered through the Allen Bradley 2711-TCI PanelView Touch Screen using the Flow Control Screen. Equipment Status Table 35.04.b.1. summarizes the proper equipment configuration for normal plant operation.
|
| Equipment Description | Status
| HS-16011 (Channel Influent Gate #1) | LOR Handswitch to REMOTE at Gate #1
| HS-16012 (Channel Influent Gate #2) | LOR Handswitch to REMOTE at Gate #2
| HS-16013 (Channel Influent Gate #3) | LOR Handswitch to REMOTE at Gate #3
| HS-16214 (Channel Influent Gate #4) | LOR Handswitch to REMOTE at Gate #4
| HS-16215 (Channel Influent Gate #5) | LOR Handswitch to REMOTE at Gate #5
| HS-16216 (Channel Influent Gate #6) | LOR Handswitch to REMOTE at Gate #6
| | |
The UV SCC controls all aspects of channel operation. The operator is responsible for entering setpoints and must place all channels in AUTO for SCC control. For further information, please reference the Trojan Technologies Operation and Maintenance Manual on the UV Disinfection System.
A contingency Plan is written to handle an unpredictable occurrence that has a reasonable chance of happening. Most Contingency Plans deal with situations where having a written procedure can help prevent loss of a unit process, handle a process upset or respond to a hazardous situation. The following is a list of Contingency Plans developed for the UV Disinfection process. The plans are kept in the Contingency Plan Notebook located in the Operator Laboratory and the Shift Supervisor Office.
A Standard Operating Procedure (SOP) is written to handle operator activities performed on a regular but not necessarily daily basis. Most SOPs deal with potentially hazardous activities making it important that a written, step-by-step procedure be available. The following is a list of SOPs developed for the UV Disinfection process. The procedures are kept in the SOP Notebook located in the Operator Laboratory and the Shift Supervisor Office.
See Section 75 Maintenance Plan for troubleshooting dealing with the operation of the sluice and slide gates, UV cleaning blower, UV system, overhead crane and effluent sampler.
The operator is responsible for reviewing the SOP on Entering the UV System Influent Channel. A confined space entry form must be filled out and properly signed before entry into the channel.
The operator is responsible for reviewing the SOP on Entering the UV Module Channels. A confined space entry form must be filled out and properly signed before entry into the channel.
The operator is responsible for reviewing the SOP on Entering the UV System Effluent Channel. A confined space entry form must be filled out and properly signed before entry into the channel.
The operator is responsible for reviewing the SOP on Entering and Cleaning the Secondary Clarifiers. A confined space entry form must be filled out and properly signed before entry into the clarifier.
Ultraviolet (UV) light may severly damage eyes and unprotected skin. The best protection against exposure to UV light is for the operator to wear long sleave shirts, full-length pants, gloves and a UV resistant face sheild when working around the modules.
35.07 Records/Sampling
35.07.a. Sampling Schedule
NAME FREQUENCY TYPE LOCATION |
<-- Previous Section | Next Section --> | |