MARINE PARK WATER RECLAMATION FACILITY - Operations and Maintenance Manual

<-- Previous Section
Home

Next Section -->
 

Section 35 - UV Disinfection

35.01General Overview
35.02Design Criteria
35.03Computer Assisted Control Strategies
35.04Operating Strategies
35.05Troubleshooting
35.06Safety
35.07Records/Sampling


35.01 General Overview

The purpose of disinfection is to destroy disease-causing organisms in the final effluent prior to ultimate discharge into the receiving water. The means of disinfection is ultraviolet (UV) radiation. Secondary effluent flows from the secondary clarifiers into a flow splitting box at the influent to the UV channels. Flow split is accomplished based on headloss over a rectangular weir. The flow in each channel passes through a manually-cleaned bar screen which intercepts materials that could foul or damage the UV lamps. A counter-weighted flap gate at the discharge end of each channel maintains a constant water surface elevation in each channel. A motorized slide gate at the entrance to each channel provides isolation when a channel is shutdown for flow pacing or maintenance.

After leaving the UV channels, effluent flows through a small withdrawal well where non-potable plant water and reuse water (wetlands enhancement and/or irrigation) can be removed from the flow stream. The remaining effluent flows through the parshall flume before discharge to the outfall structure in the Columbia River.

The UV dose is adjusted based on effluent flow measurement. Banks of UV modules are energized/de-energized and UV channels put into and out of service as plant flows vary. One bank of modules in each channel will remain energized whenever the channel is in service to base load the channel. Service hours are equalized by rotating the lead bank to the bank with the least run time every time the lead channel rotates. The flow setpoints are as follows:

Flow Rate
Number of Banks in Service
0 - 3 mgd
1.00
3 - 6 mgd
2.00
6 - 9 mgd
3.00
9 - 12 mgd
4.00
12 - 18 mgd
6.00
18 - 27 mgd
9.00
27 - 36 mgd
12.00
36 - 45 mgd
15.00
>45 mgd
18.00

Channel No.3 has the capability to operate isolated from the secondary effluent flow. Slide gates control the isolation of this channel. When wetlands treatment is not required, this channel is available to operate in parallel with the remaining channels. In addition to isolation slide gates in the influent and effluent channels, a motorized slide gate controls the channel influent flow in the same manner as the other two channels and a sluice gate is used to isolate the discharge pipe to the wetlands.

Upon expansion of the effluent treatment complex, the northern most UV channel will remain the "wetlands treatment channel" and piping to the existing "wetlands" channel No.3 will be re-routed.

The UV control system for the wetlands treatment channel is operated manually while disinfecting the wetlands flow stream and in flow pacing mode while disinfecting the plant effluent flow stream. The wetlands treatment system is not required for the plant effluent flow treatment capacity and can serve as a backup plant effluent disinfection system.

Regular cleaning and inspection of the UV lamps is required to maintain effluent disinfection quality. Cleaning involves removing the modules from the channels. To accommodate this maintenance activity a UV cleaning system is provided. A bridge crane is used to remove UV modules or an entire UV bank from the channels and transport them to the cleaning area. A curbed hose down area is provided to remove loose material from the modules. The modules or banks are then lowered into a basin where an acidic cleaning solution removes scale build-up. A diffused air system agitates the cleaning basin to further enhance material removal. A dilute concentration of citric or phosphoric acid is most commonly used as a cleaning solution.

Three UV channels will be built as part of the Phase I work. Each channel is wide enough for 23 UV modules in each bank. To meet specified treatment criteria, only 19 modules per bank are supplied. Space equal to the size of 2 modules are installed on each side of each bank for the addition of future modules. Each bank is constructed to accommodate the future number of modules. Using future modules will not increase the flow capacity of each channel, but will increase the level of disinfection achieved.

Six additional channels will be constructed at ultimate buildout. Provisions will be made so that the buildout facility will utilize the Phase I cleaning equipment, including the bridge crane, and the effluent discharge channel. Ultimate effluent flow measurement will be accomplished by removing the Phase I, or interim phase, parshall flume insert from the six-foot parshall flume provided in Phase I.

35.02 Design Criteria

DISINFECTION BASINS
Number of Basins
     Phase 13
     Phase 26 (3 existing, 3 new)
     Ultimate8 (add equipment to 2 channels)
Basin Dimensions
     Length50'-0"
     Width4'-0.5"
     Depth5'-0"
     Sidewater Depth2'-0" nominal water depth
Influent TSS30 mg/l
Peak Design Flow
     Phase 120.8 mgd
     Phase 241.6 mgd
     Ultimate63 mgd
Minimum Design Flow
     Phase 12.2 mgd
     Phase 24.4 mgd
     Ultimate6.7 mgd
UV Transmissivity65 percent
Effluent Disinfection Standard (Fecal Coliform)
     Design200 MPN/100 ml
     Future Provisions30 MPN/100 ml
 
ULTRAVIOLET DISINFECTION SYSTEM
Number of Modules
     Phase 1207
     Phase 2414
     Ultimate552
Module description
     Modules/bank23
     Lamps/module8
     Power Consumption0.26 Kw/module
Ballast TypeElectronic
Lamp ConfigurationHorizontal
 
ULTRAVIOLET CLEANING SYSTEM
Cleaning Basin
     Dimensions (LxWxD)5'x7'x6'
     LiningPolyethylene
Agitation System
     BlowerRotary Lobe
     DiffusersPVC
Overhead Bridge Crane
     Capacity1 ton
     TypeTop running
     Crane Speed70 fpm
     Trolley Speed65 fpm
     Hoist Speed45 fpm (variable)
 
EFFLUENT FLOW MEASUREMENT
TypeParshall Flume
Number of Units1
Size
     Phase I2 foot
     Ultimate6 foot
Minimum Capacity
     Phase I1.1 mgd
     Ultimate6.7 mgd
Maximum Capacity
     Phase I20.8 mgd
     Ultimate63.0 mgd

35.03 Computer Assisted Control Strategies

35.03.a. General Overview

At the MPWRF, the UV disinfection system is controlled through the System Control Center (SCC) located in the Effluent Disinfection Building. The operator uses a panelview system at the SCC to monitor alarms and change system variables. The operator can also use the SCS to monitor alarms and equipment status of the UV system.

35.03.b. Control Strategies

This section tells the operator how to interact with the SCC and the SCS systems, describes each control loop and describes how and where alarm and equipment status is transmitted.

35.03.b.1. UV Influent Channel Gates

Loop Function:Opens and closes disinfection channels to meet the needs of the disinfection system based on influent flow rate. Monitors the gate position (open/closed) and sounds an alarm if the gate fails to open or close properly.
Instrumentation:ZS-16011, ZS-16012, ZS-16013, ZS-16214, ZS-16215, ZS-16216 (Monitor OPEN/CLOSED [OC] gate position switch)
(Located at each influent gate)
Control Devices:HS-16011, HS-16012, HS-16013, HS-16214, HS-16215, HS-16216 (OPEN/STOP/CLOSE [OSC] handswitch)
(Located at each influent gate)

HS-16011, HS-16012, HS-16013, HS-16214, HS-16215, HS-16216 (LOCAL/OFF/REMOTE [LOR] handswitch)
(Located at each influent gate)
Alarms:QA-16001 (UV Channel No. 1 MAJOR ALARM)
QA-16001 (UV Channel No. 1 MAJOR ALARM)
QA-16002 (UV Channel No. 2 MAJOR ALARM)
QA-16003 (UV Channel No. 3 MAJOR ALARM)
QA-16204 (UV Channel No. 4 MAJOR ALARM)
QA-16205 (UV Channel No. 5 MAJOR ALARM)
QA-16206 (UV Channel No. 6 MAJOR ALARM)
PLC/SCS Function:Monitor OPEN/CLOSE gate position switches (OC), ZS-16011, ZS-16012, ZS-16013, ZS-16214, ZS-16215, ZS-16216

Monitor LOR handswitch REMOTE position (REMOTE), QL-16011, QL-16012, QL-16013, QL-16214, QL-16215, QL-16216

Operation:

  1. The influent gates are controlled through the SCC when the LOR handswitch is placed in REMOTE. The SCC opens and closes the gates based on the flow and selected channel orientation (see Table 1 section 35.01). The operator can monitor the position of each gate using the SCS located in the Operator Laboratory and in the Administration Building.

    By placing the LOR handswitch in LOCAL, the operator can manually open and close the gates using the OSC handswitch.

  2. If the gate fails to open or close properly, MAJOR ALARM QA-1600X will sound. This alarm is displayed on the SCS located in the Operator Laboratory and in the Administration Building. To reset the PLC/SCS the gate must be placed in its proper position (either open or closed). A COMMON UV DISINFECTION SYSTEM ALARM (QA-16000) will also occur. This alarm is displayed on the SCS, on LCP-12 and activates the Alarm Autodialer. Resetting the MAJOR ALARM will also reset the COMMON UV ALARM.

35.03.b.2. UV Disinfection Channel

Loop Function:Turns on and shuts off UV lamps to meet the needs of the disinfection system based on the influent flow. Monitors lamp intensity, single and multiple lamp failures, and checks lamp module performance. The system also monitors run times for each individual module so the operator can track lamp usage. If the SCC detects any failure in the UV lamp array, it will generate an alarm.
Instrumentation:Allen-Bradley 2711-TCI PanelView Touch Screen
(Located on LP-16000)
Alarms:The SCC will display the following alarm messages:
  • Low UV intensity for all modules
  • Single lamp failures
  • Adjacent lamp failures
  • Multiple lamp failures
  • Module failures
  • Communications fault
  • Slide gate failures
  • Bank failure to energize
  • PLC power failure
  • Not enough banks available for disinfection.

Operation:

  1. The operator uses the Allen-Bradley 2711-TCI PanelView Touch Screen to control and monitor the Trojan UV3000 system. The SCS computers located in the Operator Laboratory and the Administration Building can be used to monitor system operation only. The operator views the various equipment and control displays in the system by pressing the appropriate soft key on the PanelView screen. The following is a brief overview of each menu and screen available on the PanelView. For further information please reference the Trojan Technologies Operation and Maintenance Manual on the UV Disinfection System.
    • Control Menu - used to access all control screens
    • Status Menu - used to access all status screens (status screens are identical to control screens, the only difference being that no control capabilities are provided, only status of the system)
    • Flow Control Screen - used to indicate the current flow through the system. Flowpacing setpoints and deadband are set through this screen
    • Time Setup Screen - provides a time and date display. Changes to the time and date are entered through this screen
    • Mod/Lamp Status Screen - used to monitor module and lamp status. The operator uses this screen to monitor, and if desired change the Bank Mode Control
    • Channel/Bank Setup Screen - used to set up a variety of system variables. These include:
      • Lead channel rotation
      • Bank warm up delay
      • Gate response
      • Bank time off delay
      • Channel drain
      • Multiple lamp failure
      • Alarm delay
      • Lead/lag channel selection
    • UV Intensity Screen - used to monitor UV intensity for each bank
    • Last 20 Module and Lamp Faults Record Screen - used to view the last 20 module/lamp faults. The operator can scroll up or down the screen to view the entire fault record
    • Alarm Status Screen - used to monitor the status of each individual alarm. The operator can scroll up or down through the screen either by page or individually
    • Alarm History Screen - used to review the history of alarms that have occurred, listing the alarm, the time and date it occured and the time and date that it was acknowledged
    • System Overview Screen - used as an overall view of the UV system. Most of the status points and other indicators and variables are displayed on this screen.

35.03.b.3. UV Channel Drain Valves

Loop Function:Opens and closes the channel drain valves as required to meet the needs of the disinfection system based on the influent flow.
Control Devices:None provided
Alarms:QA-16161 (Channel drain valve FV-16161 failed)
QA-16162 (Channel drain valve FV-16162 failed)
QA-16163 (Channel drain valve FV-16163 failed)
QA-16264 (Channel drain valve FV-16264 failed)
QA-16265 (Channel drain valve FV-16265 failed)
QA-16266 (Channel drain valve FV-16266 failed)
PLC/SCS Function:Monitor OPEN/CLOSE channel drain valve position switches (OC), ZS-16161, ZS-16162, ZS-16163, ZS-16264, ZS-16265, ZS-16266

Determine drain valve fail to open or close alarm (FAIL), QA-16161, QA-16162, QA-16163, QA-16264, QA-16265, QA-16266

Provide sequencing of channel drain valves

Operation:

  1. The channel drain valves are completely controlled through the PLC/SCS system. The operator must use the SCS CRT to manually open or close the valves or to monitor the open/close position of the valve. The valve either opens or closes depending on the status of the UV channel. When a channel is put on line by the SCC, the PLC tells the valve to close, when the channel goes off-line, the the valve opens.

    The valve will remain in the open position until the channel goes back on line.

35.03.b.4. UV Cleaning Blower

Loop Function:Monitors the on status of the low pressure blower for the UV Cleaning Basin.
Control Devices:HS-16061 (HAND/OFF/REMOTE [HOR] handswitch)
(Located at MCC-10)

HS-16061 (START/STOP (SS) push-buttons)
(Located at MCC-10)

QL-16061 (Blower on light [ON])
(Located at MCC-10)

HS-16061 (Auxiliary START/STOP [SS] push-buttons)
(Located at the blower)
Alarms:None associated with this loop.
PLC/SCS Function:Monitor blower on status (OOR), QL-16061

Operation:

  1. There is no SCS control available for turning the UV Cleaning Blower on and off. The operator can monitor blower on status through the SCS, however, blower control is only possible at the Effluent Disinfection Building.

35.04 Operating Strategies

35.04.a. General Operating Strategy

The influent channel gates are opened and closed manually by placing the LOR in LOCAL and using the OSC handswitch. The gates are controlled by the System Control Center (SCC) when the handswitch is placed in REMOTE.

The UV banks and influent channel gates in each disinfection channel are controlled by the System Control Center (SCC, LP-16000). The operator can monitor alarms and change system variables through a programmable user interface consisting of a CRT and keyboard mounted on the SCC. The SCC receives a 4 - 20 mAdc plant flow signal from the plant PLC located in LCP-16. The SCC uses the flow signal to turn the lamp banks on and off and to open and close the channel gates. For a detailed description of operations and user adjustable parameters see the UV manufacturer's control description.

The flow pacing signal is a 4 to 20 mA analog signal produced by the plant PLC in LCP-16. When the SCC is in flow pacing mode, it receives the 4 to 20 mA signal from the plant PLC and automatically adjusts the number UV lamps that are energized and number of channels in service in proportion to the signal.

Whenever a UV channel is taken out of service (its influent gate closed), the channel drain valve at the end of the channel is opened to drain the channel. The drain valve remains open until the channel is placed back into service to prevent water from collecting in the channel.

35.04.b. Normal Operating Conditions

Note: Normal plant operation will use the PLC and the SCS CRT to enter setpoints, select equipment operating modes and monitor equipment status. If a process can be controlled manually through the SCS CRT then this will also be included in this section. Local control of equipment will be covered under Section 35.04.c., Alternate Operating Conditions.

35.04.b.1. UV Influent Channel Gates (also see Section 35.03.b.1.)

The UV System Control Center (SCC) opens and closes the gates based on the flow signal from flow meter FE/FIT-16041 located at the effluent Parshall flume. The flow setpoints are entered through the Allen Bradley 2711-TCI PanelView Touch Screen using the Flow Control Screen. Equipment Status Table 35.04.b.1. summarizes the proper equipment configuration for normal plant operation.

EQUIPMENT STATUS TABLE 35.04.b.1.
Equipment DescriptionStatus
HS-16011 (Channel Influent Gate #1)LOR Handswitch to REMOTE at Gate #1
HS-16012 (Channel Influent Gate #2)LOR Handswitch to REMOTE at Gate #2
HS-16013 (Channel Influent Gate #3)LOR Handswitch to REMOTE at Gate #3
HS-16214 (Channel Influent Gate #4)LOR Handswitch to REMOTE at Gate #4
HS-16215 (Channel Influent Gate #5)LOR Handswitch to REMOTE at Gate #5
HS-16216 (Channel Influent Gate #6)LOR Handswitch to REMOTE at Gate #6


35.04.b.2. UV Disinfection Channel (see also Section 35.03.b.2.)

The UV SCC controls all aspects of channel operation. The operator is responsible for entering setpoints and must place all channels in AUTO for SCC control. For further information, please reference the Trojan Technologies Operation and Maintenance Manual on the UV Disinfection System.

35.04.b.3. UV Channel Drain Valves

Blank.

35.04.c. Alternate Operating Conditions

Blank.

35.04.d. Startup/Shutdown Conditions

35.04.e. Key Control Data and 4 Level Alarm Table

PARAMETERS
LAL
LWL
HWL
HAL
FREQUENCY
Eff Flow (MGD)
1.5
2.0
4.5
5.0
Continuous
Eff TSS (mg/L)
0.0
0.0
20.0
25.0
5/W
Eff CBOD (mg/L)
5.0
10.0
15.0
25.0
5/W
Fecal Coliform (# colonies/100mL)
0
0
100
150
7/W
Eff NH3 (mg/L)
5
10
20
25
1/W
Eff NO3 (mg/L)
0
0
0.5
1.0
1/W

35.04.f. Contingency Plans

A contingency Plan is written to handle an unpredictable occurrence that has a reasonable chance of happening. Most Contingency Plans deal with situations where having a written procedure can help prevent loss of a unit process, handle a process upset or respond to a hazardous situation. The following is a list of Contingency Plans developed for the UV Disinfection process. The plans are kept in the Contingency Plan Notebook located in the Operator Laboratory and the Shift Supervisor Office.

35.04.g. Standard Operating Procedures

A Standard Operating Procedure (SOP) is written to handle operator activities performed on a regular but not necessarily daily basis. Most SOPs deal with potentially hazardous activities making it important that a written, step-by-step procedure be available. The following is a list of SOPs developed for the UV Disinfection process. The procedures are kept in the SOP Notebook located in the Operator Laboratory and the Shift Supervisor Office.

35.05. Troubleshooting

See Section 75 Maintenance Plan for troubleshooting dealing with the operation of the sluice and slide gates, UV cleaning blower, UV system, overhead crane and effluent sampler.

35.06. Safety

35.06.a. Confined Spaces

35.06.a.1. UV System Influent Channel

The operator is responsible for reviewing the SOP on Entering the UV System Influent Channel. A confined space entry form must be filled out and properly signed before entry into the channel.

35.06.a.2. UV Module Channels

The operator is responsible for reviewing the SOP on Entering the UV Module Channels. A confined space entry form must be filled out and properly signed before entry into the channel.

35.06.a.3. UV System Effluent Channel

The operator is responsible for reviewing the SOP on Entering the UV System Effluent Channel. A confined space entry form must be filled out and properly signed before entry into the channel.

35.06.a.4. Secondary Clarifiers

The operator is responsible for reviewing the SOP on Entering and Cleaning the Secondary Clarifiers. A confined space entry form must be filled out and properly signed before entry into the clarifier.

35.06.b. UV Light

Ultraviolet (UV) light may severly damage eyes and unprotected skin. The best protection against exposure to UV light is for the operator to wear long sleave shirts, full-length pants, gloves and a UV resistant face sheild when working around the modules.

35.07 Records/Sampling

35.07.a. Sampling Schedule

IDX #
PARAMETER
NAME
SAMPLE
FREQUENCY
SAMPLE
TYPE
SAMPLE
LOCATION
101
EFF FLOW (MGD)
Continuous
N/A
Parshall Flume Disinfection Effluent Channel
102
MAX EFF FLOW (MGD)
Continuous
N/A
Parshall Flume Disinfection Effluent Channel
103
MIN EFF FLOW (MGD)
Continuous
N/A
Parshall Flume Disinfection Effluent Channel
104
EFF TSS (mg/L)
5/W
Composite
Effluent Channel Disinfection Building
105
EFF CBOD (mg/L)
5/W
Composite
Effluent Channel Disinfection Building
106
EFF pH
7/W
Grab
Effluent Channel Disinfection Building
107
EFF D.O. (mg/L)
7/W
N/A
Effluent Channel Disinfection Building
108
EFF FECAL COLIFORM (#/100mL)
7/W
Grab
Effluent Disinfection Building Channel
109
EFF TEMP (C)
7/W
N/A
Effluent Channel Disinfection Building
110
EFF COPPER (PPB)
1/M
Grab
Effluent Channel Disinfection Building
111
EFF LEAD (PPB)
1/M
Grab
Effluent Channel Disinfection Building
112
EFF SILVER (PPB)
1/M
Grab
Effluent Channel Disinfection Building
113
EFF HARDNESS (mg/L CaCO3)
1/W
Grab
Effluent Channel Disinfection Building
114
EFF NH3 (mg/L)
1/W
Grab
Effluent Channel Disinfection Building
115
EFF NO3 (mg/L)
1/W
Grab
Effluent Channel Disinfection Building


<-- Previous Section
Home

Next Section -->