<-- Previous Section | Next Section --> | |
| 10.01 | General Overview |
| 10.02 | Design Criteria |
| 10.03 | Computer Assisted Control Strategies |
| 10.04 | Operating Strategies |
| 10.05 | Troubleshooting |
| 10.06 | Safety |
| 10.07 | Records/Sampling |
The purpose of the influent pumps is to transfer sewage from the influent wet well to the screenings facility. The Influent Pump Station consists of a wet well, two small pumps and three large pumps. The third large pump was added during Phase II construction. Previously, two small pumps or a single large pump were capable of pumping all flow to the plant. In Phase II, depending on the rate of influent flow, as many as two large pumps and two small pumps will operate. Each pump size has a second pump held in reserve in case the first pump fails or is removed from service.
The pumps in the Influent Pump Station are identical in design and function. All are heavy-duty, vertical open-shaft, dry pit, single-suction, non-clog, centrifugal sewage pumps. The pumps are equipped with adjustable frequency drives to run continuously at any speed within the specified range.
The pump station wet well contains the following design features:
The pump station dry pit area contains the following design features:
The design criteria for the Influent Pump Station Building Phase II is presented below.
| Number of Units | 2 @ 7 mgd; 3 @ 16 mgd | ||||||||||||
| Type | Vertical, dry-pit, non-clog centrifugal | ||||||||||||
Capacity, each| Small Pumps | 2 mgd minimum | 7 mgd maximum Large Pumps | 4 mgd minimum | 16 mgd maximum Total Dynamic Head | 43 feet | Horsepower | Small Pumps | 75 hp | Large Pumps | 150 hp | Drive Type, each pump | Variable speed, adjustable frequency
| |
Overall pump station size, pump spacing, and wall penetration sizes are based on the ultimate flow conditions. Additional pumping capacity will be provided in future expansions by replacing pumps with larger capacity units. With the completion of Phase II of the project, total pumping capacity is as indicated in row 2 of the table below. It is anticipated that the Phase III expansion will consist of replacing the pumps as shown in row 3 of the table below.
| Pump Capacity, mgd | Total Capacity | |||||||||||||||||||
| Phase | 1 | 2 | 3 | 4 | 5 | |||||||||||||||
| 7 | 7 | 16 | 16 | -- | 7 | 7 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | | |||||
At the MPWRF, the Influent Pumps are automatically controlled through the PLC based on the Influent Wet Well level. The operator selects which mode the PLC uses to run the Influent Pumps using the SCS located in the Marine Park Administration Building or in the Operator Laboratory. The operator uses the SCS to monitor alarms and equipment status. The PLC/SCS system also monitors the Wet Well for combustible gas level and sounds an alarm if an elevated level is detected.
This section tells the operator how to interact with the PLC and the SCS, describes each control loop and describes how and where alarm and equipment status is transmitted.
| Loop Function: | Monitor the position of the wet well gate and provide a gate closed alarm. |
| Instrumentation: | ZS-01000 (Gate OPEN/CLOSED switch) (Located at the influent wet well) |
| Control Devices: | HS-01000 (OSC handswitch) (Located at the influent wet well) |
| Alarms: | QA-01000 (G-01000 closed) |
| PLC/SCS Function: | Monitor OPEN/CLOSE gate position switches OC), ZS-01000
Provide influent gate closed alarm (GATE CLOSED), QA-01000 |
Operation:
| Loop Function: | Measures and displays the influent wet well level, provides high and low wet well alarms, monitors the level of combustible gases in the wet well and provides an LEL alarm. |
| Instrumentation: | LSH-01031 (High wet well level switch) (Located at elevation 16.5' in the wet well) LSL-01032 (Low wet well level switch) (Located at elevation 10.75' in the wet well) LE/LIT-01030, LE/LIT-01231(Wet well level sensor and transmitter) (Located in the wet well) LI-01030, wet well level (LED bar graph) (Located on LCP-01) AE/AIT-01020 (LEL combustible gas detector) (Located in the influent wet well) ASM/ASH-01020 (LEL combustible gas monitor) (Located on LCP-01) |
| Alarms: | LAH-01031 (High wet well alarm) LAL-01032 (Low wet well alarm) AAM-01020 (LEL warning alarm, LEL level > 4.5%) AAH-01020 (LEL high level alarm, LEL level > 10%) QA-01030 (Float switches and level transmitter disagree) |
| PLC/SCS Functions: | Monitor wet well high level switch and provide alarm, LAH-01031
Monitor wet well low level switch and provide alarm, LAL-01032 Monitor LEL combustible gas alarm and warning, AAM-01020, AAH-01020 Provide wet well level control and indication, LIK-01030 Determine level float switch and level transmitter disagree alarm, QA-01030 |
Operation:
| Loop Function: | Controls the speed and number of influent pumps by using the influent wet well level. Provides pump failure alarms. |
| Control Devices: | HS-01041, HS-01042, HS-01043, HS-01044 (HOR handswitch) (Located on each AFD panel) HS-01043HS-0104 HS-01044 2 HS-01041 (SS push-buttons) (Located on each AFD panel) HS-01041, HS-01042, HS-01043, HS-01044 (Auxiliary SS push-buttons)(Located at each Influent Pump) QL-01041, QL-01042, QL-01043, QL-01044 (PUMP ON light) (Located on each AFD panel) QL-01041, QL-01042, QL-01043, QL-01044 (Pump FAIL light) (Located on each AFD panel) QL-01041, QL-01042, QL-01043, QL-0104 (POWER ON light) (Located on each AFD panel) SI-01041, SI-01042, SI-01043, SI-01044 (Speed indicator) (Located on each AFD panel) SHK-01041, SHK-01042, SHK-01043, SHK-01044 (Pump manual speed control [0-100%]) (Located on each AFD panel) LI-01041, LI-01042, LI-01043, LI-01044 (Wet well level indicator) (Located on each AFD panel) |
| Alarms: | QA-01041
(Pump P-01041 RUN FAIL in REMOTE) QA-01042 (Pump P-01042 RUN FAIL in REMOTE) QA-01043 (Pump P-01043 RUN FAIL in REMOTE) QA-01044 (Pump P-01044 RUN FAIL in REMOTE) QA-01041 (Pump P-01041 LOCAL FAIL) QA-01042 (Pump P-01042 LOCAL FAIL) QA-01043 (Pump P-01043 LOCAL FAIL) QA-01044 (Pump P-01044 LOCAL FAIL) |
| PLC/SCS Functions: | Monitor pump on status (OOR), QL-01041, QL-01042, QL-01043, QL-01044
Monitor HOR handswitch REMOTE position (OOR), QL-01041, QL-01042, QL-01043, QL-01044 Monitor local pump fail from AFD and provide alarm (LOCAL FAIL), QA-01041, QA-01042, QA-01043, QA-01044 Determine pump run fail in REMOTE and provide alarm (RUN FAIL), QA-01041, QA-01042, QA-01043, QA-01044 Small pump LEAD select handswitch (LEAD1-2), HS-01040A Large pump LEAD select handswitch (LEAD 3-4), HS-01040B Provide pump sequencing Pump sequencing mode select handswitch (SMALL-SMALL/ SMALL-LARGE), HS-01040 Provide pump speed signal from level controller, LIK-01030 Monitor auxiliary STOP push-button position (SS), HS-01041, HS-01042, HS-01043, HS-01044 |
Operation:
The level in the wet well is controlled by a PID type loop controller. The level controller output is used to vary the speed of the influent pumps. The level controller uses proportional only action, since an exact level setpoint does not need to be maintained. This allows the level of the wet well to vary above the level setpoint and absorb changes in influent flow. The level controller has three different gains and setpoints that are automatically set by the PLC depending on which combination of pumps is running. See Tables 10.04.a.1. and 10.04.a.2. for gain settings.
In REMOTE mode, each pump can be started and stopped and pump speed can be adjusted by the PLC/SCS system. The two small influent pumps and the three large influent pumps function in sets in a LEAD, BACKUP or LEAD, LAG, BACKUP configuration. If both or all three pumps in a set are selected to REMOTE, the first pump placed in REMOTE is the LEAD pump. The LEAD pump may be changed by operations using the SCS CRT button on the Influent Pumping screen. If the LEAD pump fails, the LAG pump is started if it is in REMOTE. In LEAD, LAG, BACKUP configuration, if a LEAD or LAG pump fails, the BACKUP pump starts if it is in REMOTE.
There are three modes of REMOTE influent pump sequencing and control; AUTO,MANUAL, and SIMULATE. The mode selected is used for control of all five influent pumps. There is level control information for AUTO control and SMALL/SMALL and SMALL/LARGE sequencing, a MANUAL control screen for each pump, and a SIMULATE mode at the SCS CRT. When in AUTO mode, the level controller will indicate the setpoint and the current pump speed. The setpoint cannot be adjusted through the SCS CRT. One of the three setpoints is automatically set based on the number of pumps running. The manual control screen can be used to adjust individual pump speeds in the MANUAL mode. The SIMULATE mode is available for controlling pump speed based on a simulated wetwell level, such as when level transmitter maintenance is performed. The PLC/SCS is programmed for bumpless transfer between modes. Current pump speed is maintained when modes are changed. The number of pumps running may be changed to satisfy AUTO control requirements when pump control is selected to AUTO.
When selected to MANUAL mode, the operator may set the speed of the pumps and individually start and stop the pumps through the SCS CRT. From the SCS CRT, the operator may start any combination of pumps except those specifically prevented. This software interlock is provided so that the plant capacity is not exceeded.
The pumps are sequenced automatically when selected to AUTO mode. There are two pump sequencing configurations in AUTO; 2 SMALL & 2 LARGE and 1 SMALL & 3 LARGE. The pumps sequences are selected by the PLC based on the level in the wet well and the output of the level controller as indicated in Tables 10.04.a.1. and 10.04.a.2.. The operator may also manually select the sequencing configuration through the SCS CRT. The pump sequencing and control have been set up to use the most efficient speed range of the pumps and minimize flow transients when changing pump combinations.
The speed of the pumps is varied by the level controller to match the influent flow. As mentioned above, the gain and setpoint of the level controller is changed based on which combination of pumps are running.
When operating in the 2 SMALL & 2 LARGE sequencing configuration, if one of the small influent pumps fail or is taken out of REMOTE mode, the sequencing mode will automatically switch to the 1 SMALL & 3 LARGE sequencing mode.
If the pumps are running in either MANUAL or AUTO mode and the level decreases to the low-level float, the pumps will stop. This interlock automatically resets when the level in the wet well rises to the "start SMALL lead pump level". If the pumps are not running or if the pump speed is not adequate to keep up with the influent flows and the level increases to the high level float, one large and one small pump in REMOTE will start at maximum flow capacity. The pumps will again stop at the low float level.
|
|
| | Start one large and one small pump at maximum flow capacity.
| | Maximum working wet well level.
| | Start large pump and stop second small pump, set level controller gain to deliver 13 MGD to 21 MGD between el. 12.75 ft. and 14 ft. with the large and small pump running in parallel.
| | Large and small pump level setpoint.
| | Stop large pump and start second small pump, set level controller gain to deliver 6 MGD to 14 MGD between el. 12 ft. and 13.25 ft.
| | Start second small pump, set level controller gain to deliver same as above with both small pumps running in parallel.
| | Two small pumps level setpoint.
| | Stop second small pump, LEAD small pump continues running, set level controller gain to deliver 2 MGD to 7 MGD between el. 11 ft. and 12.5 ft.
| | Start LEAD small pump, set level controller gain to deliver same as above.
| | Small pump level setpoint. Minimum wet well level.
| | Stop small pump.
| | Low level alarm switch. All pumps stopped.
| | |||||||||||||||||||
|
|
| | High level alarm switch. Start one large and one small pump at maximum flow capacity.
| | Maximum working wet well level.
| | Start small pump, set level controller gain to deliver 15 MGD to 21 MGD between el. 13 ft. and 14 ft. with the large and small pumps running in parallel.
| | Large and small pump level setpoint.
| | Stop small pump, set level controller gain to deliver 6 MGD to 16 MGD between el. 12 ft. and 13.5 ft.
| | Start large pump and stop small pump, set level controller gain to deliver same as above.
| | Large pump level setpoint.
| | Stop large pump and start small pump, set level controller gain to deliver 2 MGD to 7 MGD between el. 11 ft. and 12.5 ft.
| | Start small pump, set level controller gain to deliver same as above.
| | Small pump level setpoint. Minimum wet well level.
| | Stop small pump.
| | Low level alarm switch. All pumps stopped.
| | |||||||||||||||||||
Note: Normal plant operations will use the PLC and the SCS CRT to enter setpoints, select equipment operating modes and monitor equipment status. If a process can be controlled manually through the SCS CRT then this will also be included in this section. Local control of equipment will be covered under section 10.04.c. Alternate Operating Conditions.
The operator can open and close the Influent Wet Well Gate only at the wet well. This gate cannot be opened or closed using the SCS CRT. However, the position of the gate, either opened or closed, is monitored by the PLC and this information can be called up on the Influent Pumping Overview screen. Except when cleaning the trash rack or inspecting the wet well, the gate will be left open. If the gate is closed for any reason, an alarm will sound. Equipment Status Table 10.04.b.1. summarizes the proper equipment configuration for normal plant operation.
|
| | |||||
The influent pumps can be run either in MANUAL, SIMULATE or AUTO through the PLC/SCS system. These SCS CRT controls are located on the Influent Pump Controller screen. From this screen, the operator can select either AUTO, MANUAL or SIMULATE modes, the pump configuration (2 SMALL & 2 SMALL or 1 SMALL & 3 LARGE) and the LEAD, LAG, BACKUP pump for each set of pumps. In AUTO the PLC controls the speed of the influent pumps based on the Wet Well level. In MANUAL the operator sets the pump speed and must monitor the Wet Well level. In SIMULATE, the operator sets a simulated wetwell level to maintain a pump speed and configuration while the level transmitters are being serviced. The operator uses the SCS CRT controls located on the Influent Pump Control screen for manual control of pumps and Wet Well level information. Equipment Status Table 10.04.b.2. summarizes the proper equipment configuration for normal plant operation.
|
| Equipment Description | Status
| P-01041 (Influent Pump #1) | HOR Handswitch to REMOTE at AFD-01041
| P-01042 (Influent Pump #2) | HOR Handswitch to REMOTE at AFD-01042
| P-01043 (Influent Pump #3) | HOR Handswitch to REMOTE at AFD-01043
| P-01044 (Influent Pump #4) | HOR Handswitch to REMOTE at AFD-01044
| P-01245 (Influent Pump #5) | HOR Handswitch to REMOTE at AFD-01245
| Influent Pump Suction Valve | Open on all pumps
| Influent Pump Discharge Valve | Open on all pumps
| | |
For AUTO operation use the following:
| Pump Control Mode | Select AUTO on SCS CRT for PLC control of pump speed and sequencing |
| HS-01040A | Selects either P-01043 or P-01044 as the LEAD (Small pump LEAD selector pushbutton) pump using the SCS CRT |
| HS-01040B | Selects either P-01041, P-01042 or P-01245 as the (Large pump LEAD selector pushbutton) LEAD pump using the SCS CRT |
| HS-01040 | Selects either SMALL-SMALL or SMALL- (Pump sequencing configuration select LARGE sequencing mode using the SCS CRT pushbutton) |
For MANUAL operation use the following:
| Pump Control Mode | Select MANUAL on SCS CRT for operator control of pump speed and sequencing |
| SHK-01041, SHK-01042, SHK-01043, SHK-01044 (Pump manual speed control) | Set pump speed for 0 - 100% on the pump(s) to be run |
Note: This section covers plant operations when the PLC has failed and the SCS CRT cannot be used as described in section 10.04.b. All equipment control and monitoring is done locally either at the MCC, the AFD panel or the local panel.
| PARAMETERS | LAL | LWL | HWL | HAL | FREQUENCY |
| Influent Flow (MGD) | 2.0 | 2.5 | 7.5 | 8.0 | Continuous |
| Max Inf Flow (MGD) | 8.0 | 9.0 | 11.0 | 12.0 | Continuous |
| Min Inf Flow (MGD) | 2.0 | 2.5 | 4..5 | 5.0 | Continuous |
A contingency Plan is written to handle an unpredictable occurrence that has a reasonable chance of happening. Most Contingency Plans deal with situations where having a written procedure can help prevent loss of a unit process, handle a process upset or respond to a hazardous situation. The following is a list of Contingency Plans developed for the Influent Pumping process. The plans are kept in the Contingency Plan Notebook located in the Operator Laboratory and the Shift Supervisor Office.
A Standard Operating Procedure (SOP) is written to handle operator activities performed on a regular but not necessarily daily basis. Most SOPs deal with potentially hazardous activities making it important that a written, step-by-step procedure be available. The following is a list of SOPs developed for the Influent Pumping process. The procedures are kept in the SOP Notebook located in the Operator Laboratory and the Shift Supervisor Office.
See Section 75 Maintenance Plan for troubleshooting dealing with the operation of the influent pumps, influent wet well gate valve and the level sensors located in the influent wet well.
The operator is responsible for reviewing the SOP on Cleaning the Influent Wet Well Trash Rack. A confined space entry form must be filled out and properly signed before entry into the wet well.
Proper lockout procedures are to be followed any time the influent pumps are serviced.
10.05. Troubleshooting
10.06. Safety
10.06.a. Confined Spaces
10.06.a.1. Influent Wet Well
10.06.b. Lockout/Tagout
10.06.b.1 Influent Pumps
10.07 Records/Sampling
10.07.a. Sampling Schedule
NAME FREQUENCY TYPE LOCATION Removal Area Removal Area Removal Area |
<-- Previous Section | Next Section --> | |