MARINE PARK WATER RECLAMATION FACILITY - Operations and Maintenance Manual

<-- Previous Section
Home

Next Section -->
 

Section 10 - Influent Pumping

10.01General Overview
10.02Design Criteria
10.03Computer Assisted Control Strategies
10.04Operating Strategies
10.05Troubleshooting
10.06Safety
10.07Records/Sampling


10.01 General Overview

The purpose of the influent pumps is to transfer sewage from the influent wet well to the screenings facility. The Influent Pump Station consists of a wet well, two small pumps and three large pumps. The third large pump was added during Phase II construction. Previously, two small pumps or a single large pump were capable of pumping all flow to the plant. In Phase II, depending on the rate of influent flow, as many as two large pumps and two small pumps will operate. Each pump size has a second pump held in reserve in case the first pump fails or is removed from service.

The pumps in the Influent Pump Station are identical in design and function. All are heavy-duty, vertical open-shaft, dry pit, single-suction, non-clog, centrifugal sewage pumps. The pumps are equipped with adjustable frequency drives to run continuously at any speed within the specified range.

The pump station wet well contains the following design features:

The pump station dry pit area contains the following design features:

10.02 Design Criteria

The design criteria for the Influent Pump Station Building Phase II is presented below.

Number of Units2 @ 7 mgd; 3 @ 16 mgd
TypeVertical, dry-pit, non-clog centrifugal
Capacity, each
     Small Pumps2 mgd minimum
7 mgd maximum
     Large Pumps4 mgd minimum
16 mgd maximum
Total Dynamic Head43 feet
Horsepower
     Small Pumps75 hp
     Large Pumps150 hp
Drive Type, each pumpVariable speed, adjustable frequency

Overall pump station size, pump spacing, and wall penetration sizes are based on the ultimate flow conditions. Additional pumping capacity will be provided in future expansions by replacing pumps with larger capacity units. With the completion of Phase II of the project, total pumping capacity is as indicated in row 2 of the table below. It is anticipated that the Phase III expansion will consist of replacing the pumps as shown in row 3 of the table below.

Pump Capacity, mgdTotal Capacity
Phase12345
I
771616--
23
II
77161616
48
III
1616161616
64

10.03 Computer Assisted Control Strategies

10.03.a. General Overview

At the MPWRF, the Influent Pumps are automatically controlled through the PLC based on the Influent Wet Well level. The operator selects which mode the PLC uses to run the Influent Pumps using the SCS located in the Marine Park Administration Building or in the Operator Laboratory. The operator uses the SCS to monitor alarms and equipment status. The PLC/SCS system also monitors the Wet Well for combustible gas level and sounds an alarm if an elevated level is detected.

10.03.b Control Strategies

This section tells the operator how to interact with the PLC and the SCS, describes each control loop and describes how and where alarm and equipment status is transmitted.

10.03.b.1. Influent Wet Well Gate

Loop Function:Monitor the position of the wet well gate and provide a gate closed alarm.
Instrumentation:ZS-01000 (Gate OPEN/CLOSED switch)
(Located at the influent wet well)
Control Devices:HS-01000 (OSC handswitch)
(Located at the influent wet well)
Alarms:QA-01000 (G-01000 closed)
PLC/SCS Function:Monitor OPEN/CLOSE gate position switches OC), ZS-01000
Provide influent gate closed alarm (GATE CLOSED), QA-01000

Operation:

  1. The wall penetration for the incoming 60 inch raw sewage pipe is provided with a motorized sluice gate that allows the operator to isolate the wet well. To open or close influent gate G-01000, use handswitch HS-01000. The influent gate can be opened or closed only at the wet well. There is no remote operational capability available.

  2. Switch ZS-01000 shows the position of the gate (either open/closed). Sensor ZI-01000 monitors the position of ZS-01000 and sends this information to the PLC. If ZI-01000 shows that the gate is closed, the PLC initiates alarm QA-01000 which is displayed on LCP-01 and the SCS located in the Operator Laboratory and in the Administration Building. If this alarm occurs during the period when the plant is unoccupied, the critical alarm dialer will call out this alarm. The gate must be reopened to reset the PLC/SCS.

10.03.b.2. Influent Wet Well

Loop Function:Measures and displays the influent wet well level, provides high and low wet well alarms, monitors the level of combustible gases in the wet well and provides an LEL alarm.
Instrumentation:LSH-01031 (High wet well level switch)
(Located at elevation 16.5' in the wet well)

LSL-01032 (Low wet well level switch)
(Located at elevation 10.75' in the wet well)

LE/LIT-01030, LE/LIT-01231(Wet well level sensor and transmitter)
(Located in the wet well)

LI-01030, wet well level (LED bar graph)
(Located on LCP-01)

AE/AIT-01020 (LEL combustible gas detector)
(Located in the influent wet well)

ASM/ASH-01020 (LEL combustible gas monitor)
(Located on LCP-01)
Alarms:LAH-01031 (High wet well alarm)
LAL-01032 (Low wet well alarm)

AAM-01020
(LEL warning alarm, LEL level > 4.5%)

AAH-01020
(LEL high level alarm, LEL level > 10%)

QA-01030
(Float switches and level transmitter disagree)
PLC/SCS Functions:Monitor wet well high level switch and provide alarm, LAH-01031

Monitor wet well low level switch and provide alarm, LAL-01032

Monitor LEL combustible gas alarm and warning, AAM-01020, AAH-01020

Provide wet well level control and indication, LIK-01030

Determine level float switch and level transmitter disagree alarm, QA-01030

Operation:

  1. Ultrasonic level sensor LE-01030 monitors the wet well level. The signal from LE-01030 is sent to LIT-01030 which sends the level reading as an analog input to the PLC. The wet well level is shown on LCP-01 as LED bar graph LI-01030 and on the SCS located in the Operator Laboratory and in the Administration Building.

    The PLC uses the wet well level input from LE/LIT-01030 to set the influent pump speed and wet well setpoints (see section 10.03.b.3.).

  2. Level floats LSH-01031 and LSL-01032 send high and low wet well alarms LAH-01031 and LAL-01032 to the PLC. LAH-01031 is displayed on LCP-01 and on the SCS. LAL-01032 is displayed only on the SCS. If the high wet well alarm occurs during the period when the plant is unoccupied, the critical alarm dialer will call out this alarm. To reset the PLC/SCS after alarm LAH-01031, the wet well level must fall below 16.5', To reset after alarm LAL-01032, the wet well must rise above 10.75'.

  3. LEL gas sensor AE-01020 monitors LEL levels in the wet well. Transmitter AIT-01020 sends the LEL signal to the PLC. When the LEL level exceeds 4.5%, LEL alarm module ASM-01020 sends warning alarm AAM-01020 to the SCS located in the Operator Laboratory and in the Administration Building. To reset the PLC/SCS the LEL level in the wet well must fall below 4.5%. If the LEL continues to rise and exceeds 10%, LEL alarm module ASH-01020 sends LEL high level alarm AAH-01020. This alarm is displayed on LCP-01 and on the SCS. In addition, the LEL horn and beacon located at the wet well will be activated. Press the horn alarm silence button HS-01020 located at the wet well to silence the alarm horn. Reset the PLC/SCS by acknowledging the alarm condition at LCP-01.

10.03.b.3. Influent Pumps

Loop Function:Controls the speed and number of influent pumps by using the influent wet well level. Provides pump failure alarms.
Control Devices:HS-01041, HS-01042, HS-01043, HS-01044
(HOR handswitch) (Located on each AFD panel)

HS-01043HS-0104 HS-01044 2 HS-01041
(SS push-buttons) (Located on each AFD panel)

HS-01041, HS-01042, HS-01043, HS-01044
(Auxiliary SS push-buttons)(Located at each Influent Pump)

QL-01041, QL-01042, QL-01043, QL-01044
(PUMP ON light) (Located on each AFD panel)

QL-01041, QL-01042, QL-01043, QL-01044
(Pump FAIL light) (Located on each AFD panel)

QL-01041, QL-01042, QL-01043, QL-0104
(POWER ON light) (Located on each AFD panel)

SI-01041, SI-01042, SI-01043, SI-01044
(Speed indicator) (Located on each AFD panel)

SHK-01041, SHK-01042, SHK-01043, SHK-01044
(Pump manual speed control [0-100%]) (Located on each AFD panel)

LI-01041, LI-01042, LI-01043, LI-01044
(Wet well level indicator) (Located on each AFD panel)
Alarms:QA-01041
(Pump P-01041 RUN FAIL in REMOTE)

QA-01042
(Pump P-01042 RUN FAIL in REMOTE)

QA-01043
(Pump P-01043 RUN FAIL in REMOTE)

QA-01044
(Pump P-01044 RUN FAIL in REMOTE)

QA-01041
(Pump P-01041 LOCAL FAIL)

QA-01042
(Pump P-01042 LOCAL FAIL)

QA-01043
(Pump P-01043 LOCAL FAIL)

QA-01044
(Pump P-01044 LOCAL FAIL)
PLC/SCS Functions:Monitor pump on status (OOR), QL-01041, QL-01042, QL-01043, QL-01044

Monitor HOR handswitch REMOTE position (OOR), QL-01041, QL-01042, QL-01043, QL-01044

Monitor local pump fail from AFD and provide alarm (LOCAL FAIL), QA-01041, QA-01042, QA-01043, QA-01044

Determine pump run fail in REMOTE and provide alarm (RUN FAIL), QA-01041, QA-01042, QA-01043, QA-01044

Small pump LEAD select handswitch (LEAD1-2), HS-01040A

Large pump LEAD select handswitch (LEAD 3-4), HS-01040B

Provide pump sequencing

Pump sequencing mode select handswitch (SMALL-SMALL/ SMALL-LARGE), HS-01040

Provide pump speed signal from level controller, LIK-01030

Monitor auxiliary STOP push-button position (SS), HS-01041, HS-01042, HS-01043, HS-01044

Operation:

  1. The two small and two large influent pumps function together in a LEAD-LAG configuration. When both pumps of each pair are placed in REMOTE using the HOR handswitch, the first pump placed in REMOTE becomes the LEAD pump. LEAD pump designation can be changed using a SCS CRT handswitch (HS-01040A for pumps P-01041 and P-01042; HS-01040B for pumps P-01043 and P-01044). When all four pumps are placed in the REMOTE mode, influent pump sequencing and control is directed through the PLC/SCS system. The operator uses the SCS CRT to select either AUTO or MANUAL mode. In AUTO mode, the wet well level controller (LIK-01030) controls the level setpoint and pump speed. The setpoint cannot be adjusted through the SCS CRT. One of three wet well setpoints is automatically set based on the number of pumps running (one small; two small; one small and one large). In MANUAL mode, the operator may set the speed of the pumps and individually start and stop pumps through the SCS CRT. The operator may select to run one small pump, one large pump or a maximum of one large and one small pump.

    The pumps are sequenced automatically when in the AUTO mode. The operator may choose from one of two modes, SMALL-SMALL and SMALL-LARGE, through the SCS CRT. The PLC starts and stops pumps based on the level in the wet well and the output of the wet well controller (see Tables 1 and 2 in
    Section 10.04.a. General Operating Strategy). The level controller varies the speed of the pumps to match the plant influent flow.

  2. In the event a pump fails while the HOR handswitch is in REMOTE, a pump fail signal is sent from the AFD panel to the PLC. The PLC generates a RUN FAIL alarm (QA-0104X) which is displayed on the SCS located in the Operator Laboratory and in the Administration Building. To reset the PLC/SCS, set the HOR handswitch to OFF. In the event that all pumps shut down and cannot be restarted by the PLC, the PLC sounds alarm QA-1040 (all PUMPS OFF). This alarm is displayed on LCP-01 and the SCS. If this alarm occurs during the period when the plant is unoccupied, the critical alarm dialer will call out this alarm. To reset the PLC/SCS, an Influent Pump must be started. If the operator is running a pump in HAND and the pump fails, the PLC will generate a LOCAL FAIL alarm. This alarm is displayed at the AFD panel as well as on the SCS. Set the HOR handswitch to OFF to reset the PLC/SCS system.

10.04 Operating Strategies

10.04.a. General Operating Strategy

The level in the wet well is controlled by a PID type loop controller. The level controller output is used to vary the speed of the influent pumps. The level controller uses proportional only action, since an exact level setpoint does not need to be maintained. This allows the level of the wet well to vary above the level setpoint and absorb changes in influent flow. The level controller has three different gains and setpoints that are automatically set by the PLC depending on which combination of pumps is running. See Tables 10.04.a.1. and 10.04.a.2. for gain settings.

In REMOTE mode, each pump can be started and stopped and pump speed can be adjusted by the PLC/SCS system. The two small influent pumps and the three large influent pumps function in sets in a LEAD, BACKUP or LEAD, LAG, BACKUP configuration. If both or all three pumps in a set are selected to REMOTE, the first pump placed in REMOTE is the LEAD pump. The LEAD pump may be changed by operations using the SCS CRT button on the Influent Pumping screen. If the LEAD pump fails, the LAG pump is started if it is in REMOTE. In LEAD, LAG, BACKUP configuration, if a LEAD or LAG pump fails, the BACKUP pump starts if it is in REMOTE.

There are three modes of REMOTE influent pump sequencing and control; AUTO,MANUAL, and SIMULATE. The mode selected is used for control of all five influent pumps. There is level control information for AUTO control and SMALL/SMALL and SMALL/LARGE sequencing, a MANUAL control screen for each pump, and a SIMULATE mode at the SCS CRT. When in AUTO mode, the level controller will indicate the setpoint and the current pump speed. The setpoint cannot be adjusted through the SCS CRT. One of the three setpoints is automatically set based on the number of pumps running. The manual control screen can be used to adjust individual pump speeds in the MANUAL mode. The SIMULATE mode is available for controlling pump speed based on a simulated wetwell level, such as when level transmitter maintenance is performed. The PLC/SCS is programmed for bumpless transfer between modes. Current pump speed is maintained when modes are changed. The number of pumps running may be changed to satisfy AUTO control requirements when pump control is selected to AUTO.

When selected to MANUAL mode, the operator may set the speed of the pumps and individually start and stop the pumps through the SCS CRT. From the SCS CRT, the operator may start any combination of pumps except those specifically prevented. This software interlock is provided so that the plant capacity is not exceeded.

The pumps are sequenced automatically when selected to AUTO mode. There are two pump sequencing configurations in AUTO; 2 SMALL & 2 LARGE and 1 SMALL & 3 LARGE. The pumps sequences are selected by the PLC based on the level in the wet well and the output of the level controller as indicated in Tables 10.04.a.1. and 10.04.a.2.. The operator may also manually select the sequencing configuration through the SCS CRT. The pump sequencing and control have been set up to use the most efficient speed range of the pumps and minimize flow transients when changing pump combinations.

The speed of the pumps is varied by the level controller to match the influent flow. As mentioned above, the gain and setpoint of the level controller is changed based on which combination of pumps are running.

When operating in the 2 SMALL & 2 LARGE sequencing configuration, if one of the small influent pumps fail or is taken out of REMOTE mode, the sequencing mode will automatically switch to the 1 SMALL & 3 LARGE sequencing mode.

If the pumps are running in either MANUAL or AUTO mode and the level decreases to the low-level float, the pumps will stop. This interlock automatically resets when the level in the wet well rises to the "start SMALL lead pump level". If the pumps are not running or if the pump speed is not adequate to keep up with the influent flows and the level increases to the high level float, one large and one small pump in REMOTE will start at maximum flow capacity. The pumps will again stop at the low float level.

TABLE 10.04.a.1. - SMALL-SMALL sequencing mode
Wet Well
Elevation
Action
Increasing
Decreasing
 
16.5
 Start one large and one small pump at maximum flow capacity.
14
 Maximum working wet well level.
13.25
 Start large pump and stop second small pump, set level controller gain to deliver 13 MGD to 21 MGD between el. 12.75 ft. and 14 ft. with the large and small pump running in parallel.
12.75
 Large and small pump level setpoint.
 
12.75
Stop large pump and start second small pump, set level controller gain to deliver 6 MGD to 14 MGD between el. 12 ft. and 13.25 ft.
12.5
 Start second small pump, set level controller gain to deliver same as above with both small pumps running in parallel.
12
 Two small pumps level setpoint.
 
12
Stop second small pump, LEAD small pump continues running, set level controller gain to deliver 2 MGD to 7 MGD between el. 11 ft. and 12.5 ft.
11.5
 Start LEAD small pump, set level controller gain to deliver same as above.
11
 Small pump level setpoint. Minimum wet well level.
 
10.75
Stop small pump.
 
10.5
Low level alarm switch. All pumps stopped.


TABLE 10.04.a.2. - SMALL-LARGE sequencing mode
Wet Well
Elevation
Action
Increasing
Decreasing
 
16.5
 High level alarm switch. Start one large and one small pump at maximum flow capacity.
14
 Maximum working wet well level.
13.5
 Start small pump, set level controller gain to deliver 15 MGD to 21 MGD between el. 13 ft. and 14 ft. with the large and small pumps running in parallel.
13
 Large and small pump level setpoint.
 
13
Stop small pump, set level controller gain to deliver 6 MGD to 16 MGD between el. 12 ft. and 13.5 ft.
12.5
 Start large pump and stop small pump, set level controller gain to deliver same as above.
12
 Large pump level setpoint.
 
12
Stop large pump and start small pump, set level controller gain to deliver 2 MGD to 7 MGD between el. 11 ft. and 12.5 ft.
11.5
 Start small pump, set level controller gain to deliver same as above.
11
 Small pump level setpoint. Minimum wet well level.
 
10.75
Stop small pump.
 
10.5
Low level alarm switch. All pumps stopped.


10.04.b. Normal Operating Conditions

Note: Normal plant operations will use the PLC and the SCS CRT to enter setpoints, select equipment operating modes and monitor equipment status. If a process can be controlled manually through the SCS CRT then this will also be included in this section. Local control of equipment will be covered under section 10.04.c. Alternate Operating Conditions.

10.04.b.1. Influent Wet Well Gate (also see Section 10.03.b.1.)

The operator can open and close the Influent Wet Well Gate only at the wet well. This gate cannot be opened or closed using the SCS CRT. However, the position of the gate, either opened or closed, is monitored by the PLC and this information can be called up on the Influent Pumping Overview screen. Except when cleaning the trash rack or inspecting the wet well, the gate will be left open. If the gate is closed for any reason, an alarm will sound. Equipment Status Table 10.04.b.1. summarizes the proper equipment configuration for normal plant operation.

EQUIPMENT STATUS TABLE 10.04.b.1.
Equipment Description
Status
HS-01000
OPEN


10.04.b.2. Influent Pumps (also see Section 10.03.b.3.)

The influent pumps can be run either in MANUAL, SIMULATE or AUTO through the PLC/SCS system. These SCS CRT controls are located on the Influent Pump Controller screen. From this screen, the operator can select either AUTO, MANUAL or SIMULATE modes, the pump configuration (2 SMALL & 2 SMALL or 1 SMALL & 3 LARGE) and the LEAD, LAG, BACKUP pump for each set of pumps. In AUTO the PLC controls the speed of the influent pumps based on the Wet Well level. In MANUAL the operator sets the pump speed and must monitor the Wet Well level. In SIMULATE, the operator sets a simulated wetwell level to maintain a pump speed and configuration while the level transmitters are being serviced. The operator uses the SCS CRT controls located on the Influent Pump Control screen for manual control of pumps and Wet Well level information. Equipment Status Table 10.04.b.2. summarizes the proper equipment configuration for normal plant operation.

EQUIPMENT STATUS TABLE 10.04.b.2.
Equipment DescriptionStatus
P-01041 (Influent Pump #1)HOR Handswitch to REMOTE at AFD-01041
P-01042 (Influent Pump #2)HOR Handswitch to REMOTE at AFD-01042
P-01043 (Influent Pump #3)HOR Handswitch to REMOTE at AFD-01043
P-01044 (Influent Pump #4)HOR Handswitch to REMOTE at AFD-01044
P-01245 (Influent Pump #5)HOR Handswitch to REMOTE at AFD-01245
Influent Pump Suction ValveOpen on all pumps
Influent Pump Discharge ValveOpen on all pumps

For AUTO operation use the following:

Pump Control ModeSelect AUTO on SCS CRT for PLC control of pump speed and sequencing
HS-01040ASelects either P-01043 or P-01044 as the LEAD (Small pump LEAD selector pushbutton) pump using the SCS CRT
HS-01040BSelects either P-01041, P-01042 or P-01245 as the (Large pump LEAD selector pushbutton) LEAD pump using the SCS CRT
HS-01040Selects either SMALL-SMALL or SMALL- (Pump sequencing configuration select LARGE sequencing mode using the SCS CRT pushbutton)

For MANUAL operation use the following:

Pump Control ModeSelect MANUAL on SCS CRT for operator control of pump speed and sequencing
SHK-01041, SHK-01042, SHK-01043, SHK-01044
(Pump manual speed control)
Set pump speed for 0 - 100% on the pump(s) to be run

10.04.c. Alternate Operating Conditions

Note: This section covers plant operations when the PLC has failed and the SCS CRT cannot be used as described in section 10.04.b. All equipment control and monitoring is done locally either at the MCC, the AFD panel or the local panel.

10.04.d. Startup/Shutdown Conditions

10.04.e. Key Control Data and 4 Level Alarm Table

PARAMETERSLALLWLHWLHALFREQUENCY
Influent Flow (MGD)2.02.57.58.0Continuous
Max Inf Flow (MGD)8.09.011.012.0Continuous
Min Inf Flow (MGD)2.02.54..55.0Continuous

10.04.f. Contingency Plans

A contingency Plan is written to handle an unpredictable occurrence that has a reasonable chance of happening. Most Contingency Plans deal with situations where having a written procedure can help prevent loss of a unit process, handle a process upset or respond to a hazardous situation. The following is a list of Contingency Plans developed for the Influent Pumping process. The plans are kept in the Contingency Plan Notebook located in the Operator Laboratory and the Shift Supervisor Office.

10.04.g. Standard Operating Procedures

A Standard Operating Procedure (SOP) is written to handle operator activities performed on a regular but not necessarily daily basis. Most SOPs deal with potentially hazardous activities making it important that a written, step-by-step procedure be available. The following is a list of SOPs developed for the Influent Pumping process. The procedures are kept in the SOP Notebook located in the Operator Laboratory and the Shift Supervisor Office.

10.05. Troubleshooting

See Section 75 Maintenance Plan for troubleshooting dealing with the operation of the influent pumps, influent wet well gate valve and the level sensors located in the influent wet well.

10.06. Safety

10.06.a. Confined Spaces

10.06.a.1. Influent Wet Well

The operator is responsible for reviewing the SOP on Cleaning the Influent Wet Well Trash Rack. A confined space entry form must be filled out and properly signed before entry into the wet well.

10.06.b. Lockout/Tagout

10.06.b.1 Influent Pumps

Proper lockout procedures are to be followed any time the influent pumps are serviced.

10.07 Records/Sampling

10.07.a. Sampling Schedule

IDX #
PARAMETER
NAME
SAMPLE
FREQUENCY
SAMPLE
TYPE
SAMPLE
LOCATION
6
INF FLOW (MGD)
Continuous
N/A
Parshall Flumes Screening
Removal Area
7
MAX INF FLOW(MGD)
Continuous
N/A
Parshall Flumes Screening
Removal Area
8
MIN INF FLOW(MGD)
Continuous
N/A
Parshall Flumes Screening
Removal Area


<-- Previous Section
Home

Next Section -->